Signal-VK1 instructions - fire alarm and control panel. Signal-VK2 instructions - fire alarm control panel Yes, this is what I need

Signal-VK1 instructions - fire alarm and control panel.  Signal-VK2 instructions - fire alarm control panel Yes, this is what I need
Signal-VK1 instructions - fire alarm and control panel. Signal-VK2 instructions - fire alarm control panel Yes, this is what I need

User manual

Intended use
2.1 Preparing the Signal-VK2 device for use
2.1.1 Safety precautions when preparing the device.
a) When operating the device, you must comply with the current "Rules" technical operation electrical installations of consumers and safety rules for the operation of electrical installations of consumers."
b) Sources of danger in the Signal-VK2 device are:
1) terminals "~220 V" for connecting the network alternating current;
2) fuse holder on the input block (F1);
3) input winding contacts power transformer(T1).
c) Installation, installation, Maintenance produce with switched off mains voltage from the device.
d) Housing Signal-VK2 device must be securely grounded. The connection resistance between the grounding bolt and the ground loop should not exceed 0.1 Ohm. It is prohibited to use heating system pipes as grounding.
d) Electric wires must be protected from possible violation insulation in places around metal edges.
g) It is prohibited to use fuses that do not correspond to the rated value.
j) Installation and maintenance of the device must be carried out by persons qualified qualification group in terms of safety, no lower than third.

Installation procedure for Signal-VK2

a) The Signal-VK2 device is installed on walls or other structures of a protected premises in places protected from exposure to precipitation, mechanical damage and access by unauthorized persons.
b) The light signaling device must be placed in places that are clearly visible to the facility's economic authority after leaving the premises.
c) Installation of the device and warning light is carried out in accordance with RD.78.145-93 "Rules for the production and acceptance of work. Security, fire and security installations fire alarm".
G) Install the Signal-VK2 device in the following sequence:
1) determine the installation location of the device;
2) mark the fastening in accordance with Appendix A, mount the fastening elements;
3) install the battery into the device;
4) install the device on the fastening elements.
e) Carry out installation connecting lines, equipment in accordance with the project.
f) Connect external circuits (except power cord) according to Appendix B. Connect the reader for electronic identifiers Touch Memory DS1990A or “Reader-2” with the internal contact to the “TM+” terminal, and the external contact to the “TM-” terminal. Ground the device.
h) Connect the battery, observing the polarity (white wire to the “-” terminal).
i) Connect the power cord.
j) Install in desired position switches for selecting device configuration.
2.1.3 Preparation for work
a) Check the correct installation.
b) Set all configuration switches to OFF.
Check the functionality of the device in the following sequence:
1) turn on the mains power of the device. In this case, the “PIT” indicator turns on in continuous light mode;
2) bring both alarm systems back to normal by closing doors, windows, transoms, etc.;
3) if it is intended to use EI, register them in the long-term memory of the device (see clause 2.1.4).
When programming, apply symbols on the holder of each EI that correspond to the AL numbers that are controlled by this EI (for example, for AL1 and AL2 at the same time - symbol "1+2").
Issue these EIs to those responsible for arming and disarming the device and record the names of those responsible, alarm numbers and their reference numbers.
2.1.4 Registration of electronic identifiers (EI).
2.1.4.1 Limitations.
2.1.4.1.1 Total EI can be no more than 15 pieces, including master EI.
2.1.4.1.2 The same EI is not recorded twice.
2.1.4.1.3 Master EI is always recorded as influencing AL1 and AL2.
2.1.4.1.4 The recording procedure ends when the long-term memory is full (the number of recorded EIs is 15 pcs.), the master EI is presented again, or after 1 minute of inactivity without the EI contacting the device. When exiting the programming mode, the built-in sound signal turns on for 1 second.
2.1.4.2The Signal-VK2 device does not have the function of “additional recording” of EI. When initiating the recording procedure, all previously entered EI must be recorded again.
2.1.4.3 To put the device into programming mode, you must open the front cover of the device, press the built-in “Armed/Disarmed” switch, move the configuration switches “1” and “2” to the OFF position, and the limit switch on the device body must be unlocked. If these conditions are met, hold down the "PROG" button for at least 3 s. The device signals the transition to the EI programming mode with five short beeps.
2.1.4.4 Next, the device can be in two modes:
2.1.4.4.1 Mode 1. Waiting for the master EI to be presented to record the working EI into long-term memory. In the same mode, it is possible to clear all long-term memory and record a new master EI and working EI. When entering this mode, the indicators on the front panel “PIT”, “ШС1”, and “ШС2” light continuously.
2.1.4.4.2 Mode 2. Recording EI as master EI. The device enters this mode if the long-term memory is cleared or contains information that cannot be identified. When entering this mode, the indicators on the front panel “PIT”, “ShS1”, and “ShS2” glow intermittently with a frequency of 1 Hz.
In any mode, if no operations with EI were performed within 1 minute, the device goes into normal operating mode. Each presentation of any EI again sets the waiting time to 1 minute.
2.1.4.5 Description of mode 1.
2.1.4.5.1 When entering this mode, the indicators on the front panel “PIT”, “ШС1”, and “ШС2” glow continuously. The device waits for the master EI to be presented to allow the operation of writing working EIs. Only in mode 1 can the long-term memory clearing procedure be performed. In this case, all previous records are erased and cannot be restored. The procedure for clearing long-term memory will be described below.
2.1.4.5.2 If the non-master EI is applied three times, the device goes into normal operation.
2.1.4.5.3 If the supplied EI is identified as a master EI, the device goes into the working EI recording mode. In this case, the codes of previous EIs (except for the master EI) are erased.
2.1.4.5.4 In this mode, the “ШС1” indicator glows intermittently with a frequency of 1 Hz, the other indicators are turned off. This means that under these conditions the recording of EI affecting ShS1 will be made, i.e. With these EIs it will be possible to arm and disarm only ShS1. All EIs that were applied in this mode will be recorded in the long-term as affecting only ShS1.
2.1.4.5.5 To translate Signal-VK2 device In the recording mode of EI affecting ShS2, you must press the limit switch once. While the limit switch is held, the "PIT" indicator turns on. After releasing the limit switch, the "ШС2" indicator glows intermittently with a frequency of 1 Hz, the other indicators are turned off. All EIs that were presented in this mode will be recorded in long-term memory as affecting only ShS2.
2.1.4.5.6 To switch the device to the recording mode of EI affecting ShS1 and ShS2, you must press the limit switch one more time. While the limit switch is held, the "PIT" indicator turns on. After releasing the limit switch, the “ШС1” and “ШС2” indicators glow intermittently with a frequency of 1 Hz, the “PIT” indicator is turned off. All EIs that were presented in this mode will be recorded in long-term memory as affecting ShS1 and ShS2.
2.1.4.5.7 The next click on the limit switch switches the device to the recording mode of EI affecting ShS1. Each subsequent click on the limit switch alternately switches the device to the next EI recording mode.
2.1.4.6 The procedure for recording a new master EI is possible only after the procedure for erasing long-term memory.
2.1.4.7 Procedure for erasing long-term memory.
2.1.4.7.1 Erasing long-term memory is possible after entering mode 1.
2.1.4.7.2 To initiate the procedure for erasing long-term memory, it is necessary to keep the connection contacts of the EI reader closed for at least 5 s. After clearing the long-term memory, the device switches to mode 2, i.e. awaits the presentation of EI, which must be recorded as master EI.

Yes, this is what I need

Size: px

Start showing from the page:

Transcript

1 SECURITY AND FIRE RECEIPT CONTROL DEVICE “SIGNAL-VK1”, “SIGNAL-VK1” version 01 ATsDR RE Operating manual 2003

2 Contents Introduction 3 1 Description of the device Purpose of the device Characteristics Complete set Design and operation of the device Labeling Packaging 15 2 Intended use Preparing the device for use Preparing for operation Using the device 18 3 Maintenance 19 4 Maintenance 21 5 Transportation and storage 22 6 Manufacturer's guarantees 23 7 Certification information 23 Appendix A Overall and installation dimensions 24 Appendix B Electrical functional diagram 25 Appendix C Electrical connection diagram of the device 26 Appendix D Diagram for checking the functionality of the device 27 8 Certificate of acceptance and packaging 28 2

3 This operating manual is intended to study the principle of operation and operation of the alarm and fire alarm control panels PPKOP "Signal-VK1" and PPKOP /01 "Signal-VK1" used Description of the device 1.1 Purpose of the device Security and fire alarm alarm and control devices PPKOP "Signal" -VK1" and PPKOP /01 "Signal-VK1" isp.01, (hereinafter referred to as the device), is designed for centralized and autonomous protection of stores, cash registers, banks, pharmacies, institutions and other objects from unauthorized entry and fires by monitoring the state of one an alarm loop (AL) with security, fire or security-fire detectors included in it and issuing notifications to the central monitoring station (MCP) using a relay output about the alarm loop violation and the activation of detectors; on-site control of internal light signaling devices, external sound and light annunciators; control of taking/removing the device using a built-in magnetically controlled contact; providing power to detectors via the "+12 V" output; control of opening the device body using a switch; ensuring changes in operating parameters using removable jumpers The device is designed for installation inside a protected facility and is designed for round-the-clock operation The device is designed for working together with centralized monitoring consoles "Neva-10", "Neva-10M", "Tsentr-M", "Tsentr-KM", "Progress-TS", "Phobos", automated workplace "Phobos", etc. The alarm loop of the device can include: - magnetic contact alarms IO102-2, IO102-4, IO102-5, IO102-6, sensors of the “Foil” and “Wire” types; - shock-contact detectors "Window-6"; - optical-electronic, ultrasonic and radio wave detectors "Photon-6", "Photon-6A", "Photon-6B", "Photon-8", "Photon-8A", "Photon-8B", "Photon-9" ", "Foton-Sh", "Foton-SK", "Foton-SK2", "Astra-MS", "Argus-2", "Argus-3", "Echo-3", "Showcase", "Echo -3", "Echo-A", "Volna-5" and the like; - acoustic type detectors "Harp", "Glass-1", "Glass-2-1", "Glass-3"; - detectors capacitive type"Peak"; - combined security detectors "Sokol-2"; - piezoelectric detectors "Gran-2", "Shorokh-1-1"; - output circuits control panels; - thermal fire detectors "IP 101-2", "IP 103-5", "IP103-7", etc. The device has the possibility of autonomous protection when powered from an alternating current network, and in the absence of a network from a backup power source or built-in battery with the issuance of signals to external light and sound annunciators and a built-in indicator. Transmission of notifications to the monitoring station about an alarm or fire is carried out using relay contacts. The transmission of a fault notification is carried out using the "open collector" (OK) output. The device is powered from an alternating current mains voltage () V, frequency (50±1) Hz and from a built-in rechargeable battery with 3

4 rated voltage 12 V and 1.2 Ah capacity or external backup source direct current voltage (12 +2.2-0.6) V The device provides the ability to supply power to detectors at a protected facility that require a separate 12 V power supply The device is intended for installation inside a protected facility and is designed for round-the-clock operation The design of the device does not provide for its use in exposure to aggressive environments, dust, as well as in fire hazardous areas. By type of maintenance, the device is classified as a product with periodic maintenance. The average total operational duration of maintenance is no more than 0.15 hours per month The device is intended for operation in the following conditions: - operating temperature range environment from 243 to 323 K (from minus 30 to C) (without battery) and from 263 to 323 K (from minus 10 to +50 o C) with battery. - relative humidity at an ambient temperature of 298 K (+25 O C) up to 98%; - vibration loads in the range from 1 to 35 Hz with a maximum acceleration of 0.5 g In terms of protection from environmental influences, the device has an ordinary design according to OST The device belongs to single-function, restored, repaired and serviced products of group II, type 1 according to GOST Law of distribution of failure-free time work - exponential An example of recording the designation of a device when ordering it and in the documentation of other products is given in Table 1. Table 1 Designation OKP Code An example of recording when ordering a version of ATsDR ATsDR Fire alarm control and alarm control device PKOP "Signal-VK1" ATsDR TU Fire and security alarm and control device PPKOP /01 "Signal-VK1" version 01 ATsDR TU 1.2 Characteristics General requirements The device complies with the requirements of GOST R, and a set of design documentation in accordance with the ACDR. Components passed the incoming inspection in accordance with GOST in accordance with the list approved in in the prescribed manner Main parameters and dimensions The device remains operational in the supply voltage range from 187 to 242 V when powered from an alternating current network with a frequency of (50 ± 1) Hz The device remains operational in the voltage range (11.6...14.2) V from the built-in battery rechargeable battery with a nominal voltage of 12 V and a capacity of 1.2 Ah in the event of a drop in the mains voltage below 187 V. Power supply of the device 4

5 can also be carried out, if the mains voltage drops below 187 V and there is no built-in battery, from an external backup DC source with voltage (12.0 +2.2-0.6) V. When performing p, the "PIT" indicator is turned on continuous mode, and when performing p in flashing with a frequency of 1 Hz. When the battery voltage drops below 10.2 V and there is no mains voltage, the “PIT” indicator turns off. If there is mains voltage and the voltage on the battery drops to 11.6 10.2 V, the remote DC sounder is turned off (if it was turned on). The power consumed by the device from the AC network in standby mode is no more than 10 VA, and in "" mode. Alarm" no more than 15 VA Current consumed by the device from a backup source, excluding the power supply to active detectors and an external light annunciator, in standby mode when monitoring the alarm loop no more than 30 mA; in "Alarm" mode 0.7 A (with the siren on). The current consumed from the backup source, taking into account the power supply of active detectors, is no more than 90 mA when monitoring the security alarm in standby mode and no more than 0.7 A (with the siren on) in the "Alarm" mode. Number of alarm loops connected to the device (information capacity) - one The information content of the device, in accordance with GOST, is given in Table 2. Table 2 Designation of the device ATsDR Types of notifications "Norma" in AL on the monitoring station "Alarm" in AL on the monitoring station "Norma" in AL on the built-in indicator "AL" "Alarm" " in the AL to the built-in indicator "AL" "Normal" to the external DC light annunciator "Alarm" to the external DC light annunciator "Alarm" to the external DC sound annunciator "Network OK" - to the built-in indicator "PIT" "Alarm" network" - to the built-in indicator "PIT" "Power failure" to the built-in indicator "PIT" "Fire" in the alarm system to the monitoring station "Fire" in the alarm system to the built-in indicator "Alarm" and the remote light dc alarm "Fire" in the alarm loop on the remote DC sound annunciator "Fault" in the AL to the output "MALFUNCTION" "Fault" in the AL to the built-in indicator "AL" and an external light DC alarm "Fault" in the AL to an external DC sound annunciator 5

6 The device provides switching of remote light and sound annunciators and the FAULT output in accordance with Table 3. Table 3 Designation of the ATsDR device with installed Species sirens and external devices Switched current in circuits, A 12 V External sound direct current 0.6 External light direct current 0.05 with battery Output FAULT 0.1 ADDR without battery External audio direct current 0.06 External light direct current 0.05 Output FAULT 0, Device ensures operability in the following operating modes: - removed (the state of the loop is not analyzed); - transitional (violation of the alarm system is not remembered); - duty officer (alarm control); - alarms (violation of alarm system is remembered); - malfunction (short circuit or interruption of the alarm loop. The violation of the alarm loop is not remembered); - fire (violation of AL is remembered) Depending on the position of the removable jumpers “1”, “2” and “AKK” the device provides functions in accordance with those specified in Table 4. Table 4 “1” “2” Alarm Delay for turning on the siren yes yes Security , 30 sec with automatic re-arming and saving of alarm indication yes no Security, 30 sec with forced control no yes Security, 0 sec with forced control no no Firefighter - "AKK" Installed Must be installed when there is no battery Removed Must be removed when the battery is connected When installed jumpers "1" and "2" in mode burglar alarm repeated violation of the alarm system leads to re-enablement sounder for 2 minutes, while the indicator of the "ShS" device and the warning light continue to glow intermittently. The sounder is activated with a delay of 30 s. When jumper "1" is installed and jumper "2" is removed in the security alarm mode, when the device is in alarm mode, restoration of the alarm system and its repeated violation does not lead to the activation of the sounder, while the sounder after the first violation of the alarm system turns on with a delay of 30 s . 6

7 When jumper “1” is removed and jumper “2” is installed in the security alarm mode when the device is in alarm mode, restoration of the alarm system and its repeated violation does not lead to the activation of the sound annunciator, while the audio alarm is turned on immediately after the first violation of the alarm system. When jumpers “1” and “2” are removed in the fire alarm mode, the device switches to the “Fire” mode when heat or smoke fire detectors with normally closed contacts are activated. The device goes into the “Fault” mode if there is a short circuit or a break in the loop. When the "AKK" jumper is installed, the device does not analyze the state of the battery and analyzes it when the jumper is removed. The device in the security alarm mode operates in the following states: armed, disarmed, "Alarm" Arming and disarming of the device. The device is picked up and removed using a built-in magnetically controlled contact. During the operation of the magnetically controlled contact, the "ShS" indicator and the remote light annunciator go into flashing mode with a frequency of 6 Hz. The device is also picked up automatically when power is supplied. In this case, the monitoring station relay contacts close and after 60 s the “ShS” indicator and the remote warning light switch on to continuous light mode. In the transition mode, within 60 s, the “ShS” indicator and the remote light annunciator turn on intermittently for 0.25 s and do not light for 1.5 s, indicating that the transition to standby mode is in progress. Alarm violation in transient mode is not remembered, however, the monitoring station indicator opens, and the “Alarm” indicator and the remote warning light switch on to intermittent lighting mode with a frequency of 1 Hz. Removal of the device is carried out by bringing a magnet to the activation zone of the magnetically controlled contact, this turns off the "AL" indicator, remote light and sound (if it was turned on) alarms, and the monitoring station relay contacts open. Modes and states of the device when the AL status changes (normal or broken) in the security mode mode depend on the state of the alarm loop (armed or disarmed) as follows: - if the alarm loop is disarmed, the “disarmed” mode is provided, the alarm loop state is not analyzed, the alarm loop status indicator is turned off, the monitoring station relay contacts are open, the light and sound alarms are turned off ; - after arming, the device provides a transitional mode (violation of the alarm system is not memorized by the device, the “Alarm Alarm” indicator and the light annunciator display the status of the alarm loop, blinking at a frequency of 1 Hz, if it is violated, they light up intermittently (0.25 s lights up and 1.5 s c does not light) - if not violated, the monitoring station relay contacts are open if the alarm loop is violated, and closed if the alarm loop is not violated). If during arming the alarm system is initially violated for more than 60 s, then the transition mode continues until the alarm loop is restored. After this, after 1 s the device goes into standby mode. After the end of the transition mode, the “ShS” indicator and the warning light light up continuously, the monitoring station relay contacts close, and the device goes into standby mode; - if the alarm system is violated in standby mode, the device goes into alarm mode with the “Alarm Alarm” indicator and light alarm switching on in a flashing mode, opening 7

8 contacts of the monitoring station relay, turning on the sounder for 2 minutes and remains in this mode until it is disarmed. With jumpers “1” and “2” installed in the security alarm mode, after turning off the sounder and restoring the alarm system, the device after 60 s goes into standby mode (automatic re-arming), the monitoring station contacts close, while the indicator “Alarm” and the light alarm remain in flashing mode. A new activation of the alarm system leads to the activation of the sound alarm for 2 minutes (in the presence of mains power and a depleted battery, the device remains operational, however, the siren will turn off when the minimum permissible voltage on the battery is reached), the opening of the monitoring station relay contacts, without changing the state of the "Alarm" indicator and warning light. The sounder is activated with a delay of 30 s. When jumper "1" is installed, jumper "2" is removed in the security alarm mode, when the device is in alarm mode, restoration of the alarm system and its repeated violation does not lead to the activation of the sound annunciator, while the sound annunciator turns on after the first violation of the alarm system with a delay of 30 s . When jumper “1” is removed, jumper “2” is installed in the security alarm mode, when the device is in alarm mode, restoring the alarm system and its repeated violation does not lead to the activation of the sound annunciator, while the sound annunciator turns on immediately after the first violation of the alarm system. In all sub-modes of the security alarm, when the device is opened, an “Alarm” signal is generated, as when a sensor with normally closed or normally open contacts is triggered. The device in fire alarm mode operates in the following states: armed, fault, fire. Device states when the AL state changes (normal or violated) depend as follows: - within 15 s after turning on the power, the device provides a transient mode and does not remember violations of the alarm system; - after 15 s the device switches to the “Armed” state; - when a heat or smoke fire detector with normally closed contacts opens, the device closes the contacts of the monitoring station relay, turns on the sound alarm in the “Fire” mode for 4 minutes, switches the “ShS” indicator and the light alarm to the flashing “Fire” mode; - when the AL opens or closes, the device opens the FAULT output, turns on the sound alarm in the “Fault” mode, turns on the “AL” indicator and the light alarm in the “Fault” mode. When the loop is restored, the device goes into the “Armed” state; - when the device case is opened, a “Fault” signal is also generated; - to switch the device to the “Armed” state from the “Fire” state, it is necessary to bring the magnet from the device kit into the zone of influence on the magnetically controlled contact. The device switches to the “Armed” state after 15 s. The device ensures that the indication is turned off and the battery is turned off in the event of a loss of voltage in the AC mains and the voltage on the battery is less than (11.0 ± 0.6) V in standby mode and less than (9.0 ±0.6) in “Alarm” or “Fire” mode with the siren on. In case of power failure 8

9 AC indicator "PIT" turns on intermittently with a frequency of 1 Hz. The device provides a "PIT" indication, which displays the state of the device's supply voltage, and issues the following notifications: - "Network OK" - the "PIT" indicator is turned on when the AC mains voltage is more than 187 V; - “Network failure” - the “PIT” indicator glows intermittently with a frequency of 1 Hz when there is no voltage in the AC network; - "Power failure" - the "PIT" indicator is turned off when the voltage in the backup power supply circuit (battery) is less than (11.0±0.6) V in standby mode and less than (9.0±0.6) in "" mode Alarm", "Fire" and in the absence of voltage in the AC mains Duration of operation of the device from a built-in backup battery with a capacity of 1.2 Ah without additional external consumers is at least 24 hours in standby mode and at least 3 hours in the "Alarm", " Fire" When security and fire detectors are switched on in the alarm loop, the device is in standby mode with the following alarm loop parameters: 1) the resistance of the alarm loop wires excluding the remote element is no more than 100 Ohms; 2) leakage resistance between the AL wires or each wire and the “ground” - at least 20 kΩ The device remains in standby mode when the AL is violated for a time of less than 50 ms (250 ms for the fire alarm mode) with an AL resistance of (2 6) kΩ ± 10% taking into account the resistance of the remote element, as well as with a slow change in the resistance of the alarm loop in the above range at a rate of up to 10% in 1 hour (only for the security alarm mode) The device switches to the "Alarm" mode when the resistance of the security alarm loop leaves the range (2 6) com ±10% for a time of 70 ms or more, as well as with an abrupt change in the resistance of the security loop by 10% or more relative current value in the range (2 6) com ±10%. The device goes into the "Fire" state when the thermal or smoke detector with normally closed contacts. The device goes into the "Fault" state when the loop opens or closes for a time of 300 ms or more (the resistance of the loop increases by more than 50 ohms or decreases to less than 100 ohms). The device provides an alarm loop at the input in standby mode constant pressure from 10 to 14 V If the alarm loop breaks, the voltage at the alarm loop input is no more than 14 V The magnitude of the ripple voltage in the alarm loop is no more than 20 mV (rms value) The device provides power supply to active detectors with the following parameters: 1) supply voltage - (12+1.8- 2.2) V; 2) current consumption - no more than 60 mA. The magnitude of the ripple voltage at the power supply output of active detectors with a voltage of 12 V is no more than 20 mV (rms value). When powered from the mains, the device restores functionality after a short circuit (up to 60 s) of the power supply circuit of active detectors. 9

10 The device provides automatic switching power supply to the built-in rechargeable battery in the event of a power failure and back without issuing an alarm notification. The device version 01 is supplied without a battery. The device provides alarm notifications to the monitoring station by opening the relay contacts when complete shutdown power supply (in security alarm mode) The device provides transmission of “Alarm” and “Fire” notifications to the monitoring station using a relay that switches electrical circuits With maximum voltage up to 80 V and a maximum current of up to 50 mA The device is resistant to impulse noise induced in the AL with an amplitude of up to 300 V and a duration of up to 10 ms The device is resistant to the effects of electromagnetic interference in the AL in the form of sinusoidal voltage pickups with a frequency of 50 Hz and an effective voltage value of up to 1 V The device does not issue false notifications after exposure to external electromagnetic interference (EMI) of the second degree of severity according to GOST R. Radio interference created by the device during operation does not exceed the values ​​​​specified in GOST R. The device ensures compliance with the requirements of paragraphs in the following conditions: 1) working temperature ambient air from 243 to 323 K (from minus 30 to +50 o C) and from 263 to 323 K (from minus 10 to +50 o C) for a device with a battery; 2) relative humidity up to 98% at 298 K (+25 o C); 3) vibration loads in the range from 1 to 35 Hz with a maximum acceleration of 0.5 g The time of technical readiness of the device for operation, after turning on its power, is no more than 3 s. The device in the package withstands during transportation: 1) transport shaking with an acceleration of 30 m/ from 2 at a frequency of beats from 80 to 120 per minute or beats; 2) temperature from 223 to 323 K (from minus 50 to C); 3) relative humidity (95±3)% at 308 K (+35 0 C) The average time between failures of the device in standby mode is not less than an hour, which corresponds to a probability of failure-free operation of 0.97 per 1000 hours. Average time to restore an operational state device when carrying out repair work- no more than 60 minutes Average term The device service life is 10 years. The battery in the device must be replaced at least once every 5 years. The weight of the device is no more than 1.5 kg (with a battery with a capacity of 1.2 Ah) and no more than 0.8 kg (without a battery). The overall dimensions of the device are not over 151 x 157 x 71 mm. 10

11 1.3 Contents The delivery set of the device corresponds to that specified in Table 5. Table 5 Qty. on Designation Name execution ATsDR Security and fire alarm control panel PPKOP "Signal-VK1" ATsDR Security and fire alarm control panel PPKOP /01 "Signal-VK1" used. 01 Set of spare parts: Resistor OZHO TU S2-33N-0.5-4.7 kom±5% Magnet in the housing Fuse-link inserts OZHO TU VPT6-1 (0.16 A) ATsDR RE pcs pcs. 1 PC. 1 PC. 1 PC. 1 PC. 1 PC. 1 PC. Note Screw 1-4x GOST pcs. 3 pcs. Battery 12 V, 1.2 Ah 1 pc. - Supplied by separate order Security and fire alarm control panel PPKOP "Signal-VK1". Operating manual 1 copy. 1 copy Note 1 The supply of group spare parts and accessories kits is carried out under a separate contract according to the spare parts and accessories list. 2 It is allowed to supply devices with a switching device "UK-VK" to provide the ability to control circuits under 220 V AC voltage with a current of up to 0.8 A or up to 10 A through outputs to light and sound annunciators (with connection of an external power source) 1.4 Design and operation of the device The device is structurally designed in the form of a box consisting of a plastic base and a lid, appearance device and its dimensions are given in Appendix A. Fixed on the base printed circuit board with radioelements, on back side The base has two shaped and one round holes for fixing, with the help of which the device is fixed to the wall in the working position. Electrical diagram functional device is given in Appendix B. The electrical connection diagram of the device is given in Appendix B. The device consists of the following functional units: - connection unit; - input block; - rectifier; - voltage stabilizer 15 V; - keys 1, 2, 3; - voltage stabilizer 5 V; eleven

12 - processor; - coordination with the Shs; - setting the operating mode of the device; - emergency battery shutdown devices; - charging devices and coordination with the battery; - control of taking and removing the device; - supply of backup power; - output "Fault"; - protection against opening; - indicators "ШС", "ПИТ" The connection unit contains two blocks for connecting external conductors of the AC supply network, a DC light alarm, an alarm loop, a remote sounder, a +12 V reserve, an actuator to the "Fault" output, monitoring station circuits and active detectors requiring a separate power source Input block contains a mains fuse and a step-down mains transformer with a thermal fuse installed inside it. The rectifier contains a bridge rectifier and a smoothing capacitor. The +15 V voltage stabilizer contains an integral stabilizer, an output smoothing electrolytic capacitor and is designed to power active detectors, remote light and sound annunciators DC Key 1 contains a low-power relay, protective diode and resistor that limits the current in the monitoring station circuit, and is intended to supply alarm signal at the monitoring station. The control action on key 1 is supplied from the processor. Key 2 contains a transistor switch, protective diodes and is designed to control the "ShS" indicator and a remote DC light alarm. The control action on key 2 is supplied from the processor. Key 3 contains a transistor switch and is designed to control an external DC sounder. The control action is supplied to switch 3 from the processor. The +5 V voltage stabilizer contains an integrated stabilizer, two smoothing capacitors and is intended to power the processor and some consumers that require a 5 V current source. The processor contains an integrated single-chip microcontroller, circuits for setting the reference frequency, the reference voltage of the ADC and is designed to control the operation of the device, the Coordination Unit with the AL provides +12 V voltage through a limiting resistor in the AL and transmits the voltage from the AL through a resistive divider to the analog input of the processor for subsequent analysis. The unit for setting the operating modes of the device includes three removable jumpers “1”, "2", "AKK" and is intended to change the current configuration of the device. The emergency battery shutdown device consists of an electronic key, and is intended to disconnect the battery when the voltage on it drops below the permissible level. The recharging and matching devices with the battery consist of a current-limiting resistor for recharging the battery and a matching diode. 12

13 The control unit for taking and removing the device consists of a magnetically controlled contact and is designed to control the device using a magnet; The backup power supply unit is designed to connect a backup DC source with a voltage of 12 V. The backup power supply is connected to the +12 V circuit of the device through a separating diode. The OK output unit is controlled from the processor output and is designed to issue a “Fault” signal to external circuits. opening contains a limit switch and contacts for installing a removable technological jumper that blocks the limit switch and is designed to put the device into alarm mode when the case is opened. The device is supplied without a jumper. In the initial state, the external toggle switches S1 and S2 are open, the device is de-energized (Appendix B). When the toggle switch S1 is closed, a supply voltage of 220 V is supplied to the device. The device begins to operate depending on the installed configuration using jumpers “1”, “2” and “AKK”: - “Normal” mode - with AL resistance (from 2 to 6) com ±10%, in security and fire modes; - “Alarm” mode - when the loop resistance is less than 1.7 kohms or more than 5.4 kohms in security mode; - “Fault” mode when the loop resistance is less than 100 Ohms or more than 50 ohms, in fire mode; - “Fire” mode with an AL resistance greater than 5.4 kohms, but less than 40 kohms in fire mode. In the “Normal” mode, the processor closes Key 1 and Key 2, thus turning on the built-in LED indicator and the “Indicator” (external DC light annunciator). All indicators should glow continuously. In the "Alarm" mode (in security mode), i.e. if the normal state of the AL resistance is violated (the AL resistance value is less than 1.7 kΩ or more than 5.4 kΩ), the processor opens Key 1, transmitting an “Alarm” signal to the monitoring station, switches the built-in “ALR” indicator and the remote light indicator to intermittent mode glow with a blinking frequency of 1 Hz. In the “Fault” mode (in fire mode), that is, if the normal state of the loop is violated (the resistance value of the loop is less than 100 ohms or more than 50 kohms), the processor opens the OK output, transmitting the “Fault” signal to the monitoring station, switches the indicator and light alarm to intermittent lighting mode: 0.5 s on, 3.5 s off, turns on the sounder in the mode: 0.5 s on, 3.5 s off. When the normal state of the loop is restored, the processor switches to the “Normal” mode. In the "Normal" mode, all indicators glow continuously. In the "Alarm" mode, the processor opens Key 1, transmitting the "Alarm" signal to the monitoring station, switches all indicators to intermittent lighting mode with a blinking frequency of 1 Hz and closes Key 3, turning on the "Siren" (remote DC sounder) for 2 minutes. Moreover, depending on the state of jumpers “1” and “2”, the remote sounder turns on immediately upon the occurrence of the “Alarm” mode or with a delay of 30 s, or the device is automatically re-armed after the siren stops working. 13

14 In the “Fire” mode (with jumpers “1” and “2” removed), the indicator and light annunciators glow intermittently with a frequency of 1 Hz. The sounder operates in the following mode: 0.5 s on, 0.5 s off, for 4 minutes. The monitoring station relay contacts close, transmitting the “Fire” signal. In the “Fault” mode (with jumpers “1” and “2” removed), the indicator and warning light light up in the mode: 0.5 s on, 3.5 s off. The sounder operates in the following mode: 0.5 s on, 3.5 s off. The OK output opens, transmitting a "Fault" signal. When the normal state of the loop is restored, the device switches to the “Normal” mode. When an “Alarm” or “Fire” mode occurs, the processor remembers it and does not return the device to the “Normal” mode even after the loop returns from the “Alarm”, “Fire” mode to the “Normal” mode. It is possible to remove this state of the processor only by acting on a magnetically controlled contact or by completely disconnecting the supply voltage (with the built-in battery disconnected). The device can operate from a backup 12 V source connected to the connection node or from the built-in battery. The power is turned on from the backup source using toggle switch S2 (see Appendix B). If there is no mains voltage, the "PIT" indicator goes into flashing mode with a frequency of 1 Hz. Otherwise, the operation of the device is the same as with mains supply voltage. 1.5 Marking The marking of the device corresponds to the set of design documentation and contains: 1) trademark of the manufacturer; 2) symbol of the device; 3) serial number; 4) mark of conformity; 5) quarter and year of manufacture (last two digits) The marking of the external terminals of the device corresponds to the electrical schematic diagram device. Near the connection point for the mains supply voltage, the rated supply voltage of 220 V is marked. The method of application and the quality of the inscriptions and symbols provide sufficient contrast to allow the inscriptions to be read in normal lighting throughout the entire service life of the device. The marking of the consumer packaging of the device meets the requirements of GOST and contains: 1 ) trademark of the manufacturer; 2) symbol of the device; 3) number of devices; 4) month and year of packaging; 5) serial number; 6) signature or stamp of the person responsible for packaging. The marking of the transport container corresponds to the drawings of the manufacturer and contains: the trademark of the manufacturer; product designation; number of products; gross weight; month and year of packaging; has 14

15 manipulation signs: “Careful, fragile!”, “Afraid of dampness,” “Top, don’t turn over”; main, additional and informational inscriptions in accordance with GOST Packaging Preservation of devices is carried out in accordance with GOST for group of products III-3 with the option of temporary anti-corrosion protection VZ Packaging of devices is carried out in consumer packaging - cardboard box type III-I GOST, a set of spare parts is also placed there, operational documentation on the device, packed in a bag of polyethylene film GOST The edges of the bag are welded Group spare parts are placed in plastic bags. The edges of the packages are sealed. Boxes with packaged devices, list of spare parts, group spare parts (if any) are placed in transport containers - boxes type II-I GOST, lined with GOST bitumen paper. Each box (or container) contains a packing list containing the following information: 1) name and designation of devices and their quantity; 2) designation and quantity of group spare parts (if any); 3) month and year of packaging; 4) signature or stamp of the person responsible for packaging. Packing of devices in containers in accordance with GOST is allowed. Net weight - no more than 40 kg Gross weight - no more than 50 kg. 2 Intended use 2.1 Preparing the device for use Safety measures when preparing the device When operating the device, you must comply with the current “Rules for the technical operation of consumer electrical installations” and “Safety rules for the operation of consumer electrical installations.” Sources of danger in the device are: - contacts ХТ1:1 and ХТ1:3 for connecting the AC mains. Installation, installation and maintenance should be carried out with the mains voltage disconnected from the device. Do not use fuses that do not correspond to the rated value. Installation and maintenance of the device must be carried out by persons with a safety qualification group of at least three. Installation procedure The device is installed on walls or other structures of a protected premises in places protected from exposure to precipitation, mechanical damage and access by unauthorized persons. Light alarms must be placed in places that are clearly visible to the facility's economic authority after leaving the premises. 15

16 Installation of the device, light and sound alarms is carried out in accordance with the RD "Rules for the production and acceptance of work. Installation of security, fire and security and fire alarm system". Install the device in the following sequence: - determine the installation location of the device; - mark the fastening, mount the fastening elements; - install the device on the fastening elements. Install the AL and connecting lines in accordance with the diagram electrical connections given in Appendix B. Connect the connecting lines to the terminals of the device in the following sequence: - connect the wires of the external DC light signaling device to contacts 11 and 12 XT2, observing the polarity; - connect the wires of the external DC sounder to contacts 1 and 2 of the XT2, observing the polarity; - connect the AL wires to pins 7 and 8 of XT2; - connect the power supply circuits of the detectors to pins 3 and 4 of XT2, observing the polarity; - connect the remote control lines to pins 5 and 6 of XT2; - connect external “Fault” circuits to contacts 13 and 4 XT2; - connect the lines from the backup DC source to pins 9 and 10 of XT2, taking into account the polarity; - connect AC power wires to pins 1 and 3 of XT1; - The mains AC source and the backup DC source must be connected to the device through switches that are used to turn off the device. The backup power supply switch S2 must be installed in the circuit: the positive terminal of the power supply - terminal XT2:10. Switch S1 must be installed in the phase wire of the network. When turning off the device, both power sources must be turned off. Failure to turn off the backup DC source will result in its discharge. When the device is turned off for a long time, the built-in battery must be disconnected from the device. 2.2 Preparation for operation Check the correctness of the installation and check the functionality of the device when powered from an alternating current network in one of the operating modes: burglar alarm (jumpers “1” and “2” are installed) or fire alarm (jumpers “1” and “2” removed) in the following sequence. Check in security alarm mode. Put the AL into standby mode by closing doors, windows, transoms, etc. Check the operation of the device during the initial switch-on period. Apply mains voltage to the device. Within 1 minute after turning on the power, simulate the violation and restoration of the alarm system. If the alarm loop is working properly, the external DC light signaling device and the built-in indicator should glow with intermittent light for 0.25 s, off for 1.5 s, if the alarm loop is broken, with intermittent light with a frequency of 1 Hz. The DC remote sounder must be turned off. Check the delay value from the moment the alarm is violated until the sounder is turned on. The delay must be at least 30 s if the device has removable 16

17 jumpers "1" and "2" are installed, and the delay is zero if jumper "1" is removed and jumper "2" is installed. Check the operation of the device in standby mode and in alarm mode. Violate the alarm system - open front door and leave it open. Apply mains voltage to the device. The remote DC light annunciator and the built-in indicator begin to glow intermittently with a frequency of 1 Hz. The DC remote sounder must be turned off. Close the front door, and the lighting mode of the remote warning light and the built-in indicator should become intermittent - lit for 0.25 s, off for 1.5 s. After 1.5 minutes, open the front door. The remote sounder and the built-in indicator switch to a flashing alarm mode and after a delay of 30 s, the remote DC sounder turns on for 2 minutes. Close the front door. The nature of the operation of the sirens should not change. Check the ability of the device to record the activation of each detector included in the AL. Check the ability of the device to work with the centralized monitoring console in the following sequence: 1) put the device into standby mode and inform the operator at the monitoring station so that the object is protected; 2) put the device into alarm mode. The monitoring station operator must determine the violation of the alarm system. Check the operation of the device according to p when powered from a backup power source or built-in rechargeable battery. Testing in fire alarm mode. Remove jumpers "1" and "2". Place the alarm system on standby, check the serviceability of the fire detectors included in the alarm system. Check the operation of the device in the “Fault” mode and in the “Fire” mode. After 15 s after turning on the device (arming in fire mode), simulate a short circuit and a break in the alarm loop, activation of fire detectors, and restoration of the alarm loop to the standby state. Perform a violation of the alarm system (break or short circuit). The remote warning light and the built-in indicator of the device should light in the following mode: 0.5 s - on, 3.5 s off. The remote sound direct current siren must operate in the following mode: 0.5 s - on, 3.5 s off. When the AL is restored to the standby state, the light annunciators and the device indicator should turn on in continuous mode, the sound annunciator should turn off, and the device goes back into standby mode. Simulate the activation of a fire detector. The remote warning light and the built-in indicator of the device should glow intermittently with a frequency of 1 Hz. The remote sound direct current siren should operate in the following mode: 0.5 s - on, 0.5 s off and turn off after 4 minutes. Turn off the power to the device. Check the ability of the device to record the activation of each fire detector included in the AL. Check the ability of the device to work with the central monitoring console in the following sequence: 17

18 - put the device into standby mode and inform the operator at the monitoring station to take control of the object; - switch the device to the “Fault” mode and back to standby mode. The monitoring station operator must detect a break or short circuit in the fire alarm loop at the facility, and then the device goes into standby mode; - switch the device to “Fire” mode. The monitoring station operator must determine if a fire detector is activated at the site. Check the operation of the device according to p when powered from a backup power source and from a built-in rechargeable battery. 2.3 Using the device Place the object under protection in the following sequence. When operating in security alarm mode (jumpers “1” and “2” are installed). For other states of jumpers “1” and “2”, see Table 4. 1) turn on the power supplies of the device in series. Using the magnetic key included with the device, switch the device to the “Removed” mode; 2) close all windows, vents, doors, etc., on which electric contact detectors are installed, open the exit door. Using the magnetic key included with the device, switch the device to standby mode; 3) at the same time, the external light annunciator and the built-in indicator should blink, the external DC sound annunciator should not work; 4) tell the monitoring station on duty by telephone the conditional number of the object being handed over for protection, and put the handset on the device; 5) leave the protected premises and close the front door, while the flashing external DC light alarm should switch to intermittent lighting mode 0.25 s on, 1.5 s off, which indicates the restoration of the alarm loop and switching of the device to the transition mode . When operating in fire alarm mode (jumpers "1" and "2" are removed). 1) turn on the power of the device and after 15 s, use the light alarms and the device indicator to determine the normal state of the alarm system and fire detectors; 2) inform the monitoring station on duty by telephone the conditional number of the property being handed over fire department object, put the handset on the device; 3) leave the protected premises, close the front door, remote sirens should glow evenly. Disarm the object when the premises are opened in the following order. When operating in the security alarm mode (jumpers “1” and “2” are installed): 1) open the front door, while the remote light network siren and DC siren should switch to flashing operating mode; 2) approach the device, using the magnetic key included with the device, switch the device to the “Removed” mode or turn off the power of the device; 3) call the monitoring station using the subscriber phone and inform the operator that the object has been disarmed. It must be borne in mind that if the time from the moment the door is opened until the device is turned off or disarmed exceeds 30 seconds, the sounder will sound. 18

19 When operating in fire alarm mode (jumpers “1” and “2” are removed), the object is monitored by the monitoring station around the clock, while the power of the device is not turned off and the monitoring station monitors the fire alarm loop of the object around the clock via two outputs of the device: the “Fault” output and the Monitoring stations, through which, accordingly, information about alarm alarm malfunction or activation of fire detectors is transmitted to the monitoring station. 3 Maintenance Maintenance of the device is carried out according to a planned preventive system, which provides for annual maintenance. Annual maintenance work is carried out by an employee of the service organization and includes: a) checking the external condition of the device; b) performance check in accordance with section 3.1 of this manual; c) checking the reliability of the device’s fastening, the condition of the external mounting wires, contact connections. Checking the operability of the device This technique is intended for engineers and technical workers and electricians of fire alarm systems servicing technical means security and fire alarm system (TS OPS), carrying out the inspection technical condition(incoming inspection), and includes checking the functionality of the device in order to identify defects and assess their technical condition. Non-compliance of devices with the requirements specified in this methodology is grounds for filing claims with the manufacturer and calling its representative to continue the inspection and resolve the issue of eliminating defects. Checking the technical condition of devices is organized by laboratories and repair shops of security departments and is carried out by maintenance personnel who have studied the principle of operation of the device and this methodology and have qualifications of at least 3 categories of electricians of the OPS. The test is carried out under normal conditions climatic conditions according to GOST: 1) ambient air temperature - () O C; 2) relative air humidity - (45-80)%; 2) Atmosphere pressure mmHg. (84-106.7) kpa. The test is carried out using a general test bench for the device, the electrical circuit diagram of which is shown in Appendix D. Total time checking the technical condition of one device no more than 40 minutes. Notes: 1 Connect and disconnect wires during checks when the power to the device and stand is turned off. 2 All checks should be carried out taking into account the technical readiness time of the device, no more than 3 s. Check the device in the following sequence: Check the condition of the packaging and unpack the device. Check the delivery package in accordance with the ACDR RE operating manual, the presence and composition of spare parts. Make sure there is no mechanical damage to the device body. Shake the device to ensure that there is no foreign objects. 19

20 Check the fastening of the terminal block. Check the presence, compliance of the rating and serviceability of the fuses of the device. Check that the device number and production date are consistent with those specified in the manual. Control of basic technical characteristics the device is carried out using a general test stand (Appendix D). Set switches S1 S7 on the stand to the off position. Connect the stand to AC power. Turn on the NETWORK switch of the stand and use the A5 variator to set the device supply voltage (220 ± 5) V, monitoring it using the PV3 voltmeter. Turn off the NETWORK switch. Turn on the direct current source A3 and set the voltage at its output to (12±0.5) V, monitoring it using the voltmeter PV2. Install jumpers "1" and "2". Turn on the stand's POWER switch and simultaneously turn on the stopwatch. The built-in indicator of the device and the INDICATOR of the stand should glow with intermittent light for 0.25 s and do not light for 1.5 s if the loop is not broken and glow with intermittent light with a frequency of 1 Hz if it is broken. The indicator of the monitoring station stand should display the current state of the alarm loop; it lights up if the alarm loop is not broken and does not light up if it is broken. The SIREN indicator should not light up. Record the time until the device indicators and the stand INDICATOR turn on in continuous lighting mode, which should be 60 s. Briefly press the OPEN switch S2 of the stand. Using a stopwatch, measure the delay time for turning on the SIREN indicator, which should be 30 s, and then the time for turning on the SIREN indicator, which should be 2 minutes. The monitoring station indicator should turn off. Using a stopwatch, measure the blinking frequency of the built-in indicator of the device and the stand INDICATOR; determine the frequency as the quotient of the number of blinks divided by the selected time (10 s). At proper operation The flashing frequency of the device should be 1 Hz. Bring magnetic key from the device kit into the area of ​​influence on the magnetically controlled contact. While the magnetic key is held in the zone, the AL indicator of the device and the INDICATOR indicator of the stand should glow intermittently with a frequency of 6 Hz. The built-in indicator of the device and the indicators INDICATOR, SIREN and monitoring station of the stand must be turned off. Repeatedly bring the magnetic key into the affected area and remove it. The device should start working according to p Turn off the stand's NETWORK switch. Remove jumpers "1" and "2". In this case, the device is configured to operate in fire mode. Turn on the stand's POWER switch and simultaneously turn on the stopwatch. The built-in indicator of the device, the stand indicators INDICATOR, SIREN and monitoring station should not light up. Record the time until the device indicator and the INDICATOR stand indicator turn on, which should be no more than 15 s. Press the switch "Open" S2 or "Short circuit" S6 of the stand. The FAULT indicator should turn off. Using a stopwatch, measure the time when the device indicator and INDICATOR stand indicator are on and off, which should be 0.5 s and 3.5 s, respectively. Press the "Open" switch S2 or "Short circuit" S6 of the fire alarm simulator. The device should go into standby mode. 20

21 Press and release switch S5 of the stand. The monitoring station indicator should turn on. Using a stopwatch, measure the time the SIREN indicator is on in the mode: 0.5 s on, 0.5 s off, which should be 4 minutes. Turn off the stand's NETWORK switch. Install jumpers "1" and "2". Press the OPEN switch S2 and turn on the stand's NETWORK switch. Using voltmeters PV4 and PV2, measure the voltage in the AL and the power supply circuit of the detectors, which, accordingly, should be no more than (12 +1.2-1.8) V. Press the OPEN switch S2. Using a voltmeter PV1, measure the voltage in the AL and the power supply circuit of the detectors, which, accordingly, should be (10-13) V and (12.0 +1.2-1.8) V. Turn off the stand's NETWORK switch. Disconnect S1 (12 V output), INDICATOR, SIREN indicators from the stand and turn on the NETWORK switch. Using a PA3 milliammeter, measure the current consumed by the device, which should be no more than 30 mA. Turn on the RESERVE switch of the stand and turn off the switch of the NETWORK stand. The device should remain in standby mode - the monitoring station indicator should light up. Using a PA1 milliammeter, measure the current consumed by the device, which should be no more than 90 mA. Using voltmeters PV1 and PV4, measure the voltage in the AL and the power supply circuit of the detectors, which, accordingly, should be (10-13) V and (12.0+1.2-1.8) V. Make an entry in the repair log and input control funds of the OPS about the results of the inspection. 4 Current repairs List of the most common or possible malfunctions and ways to eliminate them are given in Table 4.1. The list of instrumentation required for repairs in a workshop is given in Table 4.2. approximate consumption components and materials required for maintenance and repair of the device - in table 4.3. Table 4.1 Name of malfunction, Probable Cause Elimination method external manifestation and additional signs 1 When you turn on the power supply No power supply Check for the presence of a source does not light up built-in voltage in the mains voltage in the mains LED indicator Fuses are faulty Replace the "PIT" mains power fuses in the device The LED is faulty Replace the LED Faulty Replace 2 When the mains source is turned on, the fuse thermal fuse fails Short circuit in the secondary or primary circuits of the transformer, breakdown of the bridge rectifier, breakdown of the capacitor thermal fuse Check the serviceability of the transformer, bridge rectifier, capacitor. Faulty items replace 21


GIPPO-1M security and fire alarm receiving and control device The fire and security receiving and control device "GIPPO-1M" is designed to monitor the state of the alarm loop (AL), as in stand-alone mode with switching on

1 General information SECURITY AND FIRE CONTROL DEVICE 051-1-3 UTS-1-1A USER MANUAL Thank you for choosing the "UTS-1-1A" device manufactured by NPO "Siberian ARSENAL". You purchased

POWER SOURCE BBP-200 TU 4372 002 63438766 14 CERTIFICATE OF CONFORMITY CU RU C-RU.AV24.B.04521 Series RU 0477342 PASSPORT INTRODUCTION This passport is intended for maintenance personnel to study the rules

Reception and Control Device Security and Fire Control Panel 051-1-3 UTS-1-1A OPERATION MANUAL CONTENTS GENERAL INFORMATION...2 INDICATION OF SAFETY MEASURES...2 TECHNICAL DATA...3 INSTALLATION PROCEDURE AND PREPARATION

REDUNDATED POWER SUPPLY FOR OPS "RIP-24" equipment, version 01 Label ATsDR.436534.002-01 ME61 1 BASIC TECHNICAL DATA 1.1 General information 1.1.1 Redundant power supply for OPS "RIP-24" equipment

POWER SOURCE BBP-24 TU 4372 002 63438766 14 CERTIFICATE OF CONFORMITY CU RU S-RU.AL16.B.02558 Series RU 0228076 PASSPORT INTRODUCTION This passport is intended for maintenance personnel to study the rules

POWER SUPPLIES BBP-0, BBP-0, BBP-0, BBP-00 TU 00 CERTIFICATE OF CONFORMITY CU RU S-RU.AL.B.0 Series RU 00 PASSPORT INTRODUCTION This passport is intended for maintenance personnel to study operating rules

POWER SUPPLIES BBP-0, BBP-0, BBP-0, BBP-00 TU 00 CERTIFICATE OF CONFORMITY CU RU C-RU.AV.B.0 Series RU 0 PASSPORT INTRODUCTION This passport is intended for maintenance personnel to study operating rules

TERMINAL DEVICE UO-2 OF THE NOTIFICATION TRANSMISSION SYSTEM “FOBOS-3” Operating manual ATsDR.425632.002 RE 2002 Contents Page. Introduction 1 1 Description and operation of the product 1 1.1 Purpose of the product

POWER SOURCE BBP-20M TU 4372 002 63438766 14 CERTIFICATE OF CONFORMITY CU RU S-RU.AL16.B.02558 Series RU 0228076 PASSPORT INTRODUCTION This passport is intended for maintenance personnel to study the rules

Security and fire alarm control devices PPKOP 0104059-1-4 “Signal-VKA”, series 01 PPKOP 0104059-1-4/01 “Signal-VKA”, isp.01 series 01 Operating manual ATsDR.425513.011 RE 2001 Co d e r

PASSPORT to the source uninterruptible power supply BBP-100 POWER SUPPLY BBP-100 TU 4372 006 63438766 11 CERTIFICATE OF CONFORMITY ROSS RU.ХП28.B07734 PASSPORT 1. INTRODUCTION This passport is intended for study

SECURITY AND FIRE CONTROL DEVICE QUARTZ (UTS-1-1A) option 3 OPERATING MANUAL BB02 UP001 Dear customer! Thank you for choosing our products. In the creation of modern high-quality

PASSPORT for uninterruptible power supply BBP-20, BBP-30 POWER SUPPLY BBP-20, BBP-30 TU 4372 001 63438766 12 CERTIFICATE OF CONFORMITY ROSS RU.ХП28.В07734 CERTIFICATE OF CONFORMITY ROSS RU.AG17.V1 8747

TERMINAL DEVICE UO-2 OF THE NOTIFICATION TRANSMISSION SYSTEM “FOBOS-3” Operating manual ATsDR.425632.002 RE 2007 CONTENTS Page. Introduction...4 1 Description and operation of the product...4 1.1 Purpose of the product...4

Operating instructions Redundant power supply without battery RIP-12 isp.03 for battery 7 Ah 242872 Product prices on the website: http://www.vseinstrumenti.ru/electrika_i_svet/sistemy_bezopasnosti/sistemy_pozharno-

REDUCED POWER SOURCE OF EQUIPMENT OPS "RIP-12" version. 05 Label ATsDR.436534.001-09 ET 1 BASIC TECHNICAL DATA 1.1 General information 1.1.1 Redundant power supply for OPS “RIP-12” equipment

SECURITY AND FIRE CONTROL DEVICE QUARTZ option 3 OPERATING MANUAL SAPO.425513.006 RE Certificate of Conformity C-RU.PB01.V.00877 Dear Buyer! Thank you for choosing our

POWER SOURCES BBP-0, BBP-5, BBP-20, BBP-24 PASSPORT 437 00 080570 03 PS. INTRODUCTION This passport is intended for maintenance personnel to study the rules for operating power supplies BBP-0, BBP-5,

ISO 9001 REDUCED POWER SOURCE OF OPS EQUIPMENT “RIP-12 isp. 06" Label ATsDR.436534.001-12 ET PB01 1 BASIC TECHNICAL DATA 1.1 General information 1.1.1 Redundant power supply for equipment

RECEIPT - CONTROL DEVICES SECURITY - FIRE Control Panel 0104059-2-1 "Signal VK2", Control Panel 0104059-2-1/01 "Signal-VK2" exe. 01 ATsDR.425513.013 RE Operating Manual 2002 CONTENTS Introduction 3 1 Description

REDUCED POWER SUPPLY RIP-12 isp.05 (RIP-12-8/17M1) Label ATsDR.436534.001-09 ET 1 BASIC TECHNICAL DATA 1.1 General information 1.1.1 Redundant power supply RIP-12 isp.05 (RIP-12-8 /17M1)

POWER SUPPLY MIP-12 isp.02 (MIP-12-1/P3) Label ATsDR.436434.002 ET 1 BASIC TECHNICAL DATA 1.1 General information 1.1.1 Power supply MIP-12 isp.02 (MIP-12-1/P3) ( hereinafter referred to as MIP) is intended

Inv. dub. Subp. and date Ref. Perv. appl. In return. inv. ATsDR.425513.013 CONTENTS Introduction 3 1 Description and operation of the device 3 1.1 Purpose of the device 3 1.2. Characteristics 5 1.3. Contents 22 1.4 Device

1 RESERVE-12/5 SECONDARY POWER SUPPLY REDUCED PULSE RESERVE-12/5 PASSPORT TU 4372-001-79131875-08 2 RESERVE-12/5 1. PURPOSE 1.1. Redundant secondary power supply

REDUNDATED POWER SUPPLY FOR EQUIPMENT OPS RIP-24 isp.01 (RIP-24-3/7M4) Label ATsDR.436534.002-01 1 BASIC TECHNICAL DATA 1.1 General information 1.1.1 Redundant power supply for equipment

Group of companies "ELECTRA" www.electra-n.ru SOURCE OF REDUCED POWER SUPPLY IRP 12-6 Operation manual Voluntary OP066 certification CERTIFICATE OF ACCEPTANCE Redundant source

ISO 9001 REDUNDATED POWER SOURCE OF EQUIPMENT OPS “RIP-12” version. 02P Label ATsDR.436534.001-13 ET PB01 1 BASIC TECHNICAL DATA 1.1 General information 1.1.1 Redundant power supply for equipment

Group of companies "ELECTRA" www.electra-n.ru SOURCE OF REDUCED POWER SUPPLY IRP 12-6 (24-3) Operation manual Voluntary OP066 certification CERTIFICATE OF ACCEPTANCE Redundant

1 RESERVE-12/2 SECONDARY POWER SUPPLY RESERVE REDUCED PULSE RESERVE-12/2 PASSPORT TU 4372-001-79131875-08 2 RESERVE-12/2 1. PURPOSE 1.1. Redundant secondary power supply

LLC NPO MikroKomServis REDUCED POWER SUPPLY Outdoor version RESERVE-12/5U18 (IP56) 12V 5A 18 A/h PASSPORT Operating manual TU 4372-001-79131875-08 WWW.R-BP.RU TVER, 2015

VOICE SPEAKER CONTROL DEVICE “SONATA-K-20” PASSPORT TU 4372-0-5643358-2005 POCC RU.PB6.V.0027. General information Name: CONTROL DEVICE FOR VOICE ANNOUNCEERS “SONATA-K-20” Date of manufacture:

MP06 UNINTERRUPTED POWER UNITS BBP-10, BBP-20, BBP-24 OPERATING MANUAL 4371 001 40267658 04 OM This Operating Manual is intended for study by technical maintenance personnel

VOICE ANNOUNDER CONTROL DEVICE “SONATA-KL-BR” PASSPORT TU 4372-0-5643358-2005 POCC RU.PB.6.V.0027.General information Name: VOICE ANNOUNTER CONTROL DEVICE “SONATA-KL-BR” Date of manufacture:

26.30.50.129 UNINTERRUPTED POWER SUPPLY BRP-12 version 1 Passport ATPN.436234.001-15 PS Label location Manufactured and accepted in accordance with mandatory requirements state

NPF SIGMA-IS LB-06 Linear address block (ver 4.52) Operating manual SAKI.425641.004RE SAKI.425641.004 RE 1. PURPOSE... 3 2. COMPLETENESS... 3 3. TECHNICAL CHARACTERISTICS... 4 4. DEVICE

OOO SIGMA-IS LB-06 Linear address block (ver 4.52) Operating manual SAKI.425641.004RE LB-06. Operating manual 1. PURPOSE... 3 2. COMPLETENESS... 3 3. TECHNICAL CHARACTERISTICS...

SWITCHING DEVICE UK-VK UK-VK isp.10 UK-VK isp.11 UK-VK isp.1 UK-VK isp.13 UK-VK isp.14 UK-VK isp.15 Label ATsDR.4641.00 ET 1 BASIC TECHNICAL DATA 1.1 General information 1.1.1 This label

Uninterruptible power supply "AKAT" Passport Russia Tver - 1 - UNINTERRUPTED POWER SUPPLY AKAT PASSPORT 1. INTRODUCTION This passport is intended for maintenance personnel to study operating rules

SECURITY AND FIRE CONTROL DEVICE QUARTZ OPTION 1 OPERATING MANUAL UP001 General information 1 18 Thank you for choosing the “QUARTZ” device manufactured by NPO “Siberian ARSENAL”. This product

Operating instructions Pulse secondary power supply source OPTIMUS-1230-OD Secondary power supply source OPTIMUS 1230-OD ARGP.435520.003TU is designed to provide power supply

CONTROL DEVICE FOR VOICE ANNOUNCERS "SONATA-K-L" PASSPORT CODE OKPO 43 7242 TU 4372-011-56433581-2005 S-RU.AB03.V.00025 1. General information Name: CONTROL DEVICE FOR VOICE ANNOUNCERS "SONATA" -K-L"

SECONDARY POWER SUPPLY REDUCED BBP-30 V.4 TS Technical certificate Redundant secondary power supply with filtering from mutual influence of consumers on each channel

OOO Electronic technology Uninterruptible power supplies BBP-20, BBP-25, BBP-30, BBP-35, BBP-40, BBP-50, BBP-55, BBP-24-3. Passport UNINTERRUPTED POWER SUPPLIES PASSPORT 1 INTRODUCTION This passport

Ministry of Internal Affairs Russian Federation Federal State Institution "Research Center "Security" Novosibirsk branch (NF Scientific Research Center "Security") 43 729 AC voltage stabilizer

REDUCED POWER SUPPLY RIP-12 isp.01 (RIP-12-3/17M1) Label ATsDR.436534.001-01 ET 1 BASIC TECHNICAL DATA 1.1 General information 1.1.1 Redundant power supply RIP-12 isp.01 (RIP-12-3 /17M1)

Revision 01 RU ISO 9001 A FIRE DETECTORS THERMAL MAXIMUM R T RTL-A1 RTL-A2 RTL-A3 RTL-B O PASSPORT MCI 425212.006-06 PS N Chernivtsi, Ukraine 2012 INTRODUCTION This passport is intended for

VOICE ADDRESS UNIT ARIA-BRO-R TU 4372-021-49518441-10, revision 4 1. Purpose The voice alarm unit ARIA-BRO-R (hereinafter referred to as the “product”) is designed to work as part of the ARIA voice alarm system

ISO "Orion" Voice announcement unit "Horn" Installation instructions ATsDR.425541.001 IM This instruction The installation manual contains instructions that allow you to perform basic installation and preparation steps.

RECEIPT CONTROL DEVICE SECURITY - FIRE CONTROL 0104059-6-1 “Signal VK-6” ATsDR.425513.006 RE Operating manual CONTENTS Introduction 1 1 Description and operation of the product 1 1.1 Purpose of the product 1

YANTAR BRO VOICE ADDRESS UNIT 1. Purpose The YANTAR BRO voice alarm unit (hereinafter referred to as the “product”) is designed to work as part of a voice alarm system as a generation device

Reception-Control Security-Firefighter QUARTZ device option 1 OPERATION MANUAL CONTENTS GENERAL INFORMATION...2 TECHNICAL DATA...3 DEVICE DESIGN...4 INSTALLATION PROCEDURE...5 PREPARATION FOR OPERATION...5

ISO "Orion" Voice announcement unit Horn used. 01 Installation instructions ATsDR.425541.001-01 IM This installation instructions contains instructions that allow you to perform basic installation steps and

1 GENERAL INFORMATION Thank you for choosing the device of the “Granit” family, manufactured by NPO “Sibirsky Arsenal”. This product will provide reliable protection of your facility from penetration and fire. Control and reception device

User manual

Security and fire alarm control devices PPKOP 0104059-1-5
"Signal-VK1" and Control Panel 0104059-1-5/01 "Signal-VK1" version 01,
(hereinafter referred to as the device), is designed for centralized and autonomous protection of shops, cash registers, banks, pharmacies, institutions and other objects from unauthorized entry and fires by monitoring the state of one alarm loop (AL) with security, fire or security-fire alarms included in it detectors and issuing notifications to the central monitoring station (CMS) using a relay output about alarm zone violations and detector activation; on-site control of internal light
signaling devices, external sound and light annunciators; control of taking/removing the device using a built-in magnetically controlled contact; providing power to detectors via the "+12 V" output; control of opening the housing of the Signal-VK1 device using a switch; ensuring changes in operating parameters using removable jumpers.
1.1.2 The Signal-VK1 device is designed for installation inside a protected facility and is designed for round-the-clock operation.
1.1.3 The Signal-VK1 device is designed to work together with centralized monitoring consoles “Neva-10”, “Neva-10M”, “Tsentr-M”, “Tsentr-KM”, “Progress-TS”, “Phobos”, AWP "Phobos", etc.

The alarm loop of the Signal-VK1 device can include:

- magnetic contact alarms IO102-2, IO102-4, IO102-5, IO102-6, sensors of the “Foil” and “Wire” types;
- shock-contact detectors "Window-6";
- optical-electronic, ultrasonic and radio wave detectors "Foton-6", "Foton-6A", "Foton-6B", "Foton-9", "Foton-Sh", "Foton-SK", "Foton-SK2" ", "Astra-MS", "Argus-2", "Argus-3", "Echo-3", "Showcase", "Echo-3", "Echo-A" and the like;
- acoustic type detectors "Harp", "Glass-1", "Glass-2-1", "Glass-3";
- detectors of capacitive type "Peak";
- combined security detectors "Sokol-2";
- piezoelectric detectors "Gran-2", "Shorokh-1-1";
- output circuits of control panels;
- thermal fire detectors "IP 101-2", "IP 103-5", "IP103-7", etc.
1.1.4 Signal-VK1 device has the ability to provide autonomous protection when powered from an AC network, and in the absence of a network from a backup power source or built-in battery with the issuance of signals to external light and sound annunciators and a built-in indicator.
1.1.5 Notifications about an alarm or fire are transmitted to the monitoring station using relay contacts. Fault notification is carried out using the open collector output (OK).
1.1.6 The device is powered from an alternating current mains voltage (220+22-33) V, frequency (50±1) Hz and from a built-in rechargeable battery with a rated voltage of 12 V and a capacity of 1.2 A/h or an external backup source DC voltage (12 +2.2-0.6) V.
1.1.7 The Signal-VK1 device provides the ability to supply power to detectors at a protected site that require a separate 12 V power source.
1.1.8 The device is intended for installation inside a protected facility and is designed for round-the-clock operation.
1.1.9 The design of the device does not provide for its use in conditions of exposure to aggressive environments, dust, or in fire hazardous areas.
1.1.10 Based on the type of maintenance, the device is classified as a product with periodic maintenance. The average total operational duration of maintenance is no more than 0.15 hours per month.
1.1.11 The device is intended for use in the following conditions:
- range of operating ambient temperatures – from 243 to 323 K (from minus 30 to +50 °C) (without battery) and from 263 to 323 K (from minus 10 to +50 °C) with battery.
- relative humidity at an ambient temperature of 298 K (+25 °C) – up to 98%;
- vibration loads in the range from 1 to 35 Hz with a maximum acceleration of 0.5 g.
1.1.12 In terms of protection from environmental influences, the device has
ordinary design according to OST 25 1099-83.
1.1.13 The device belongs to single-function, restored, repaired and serviced products of group II, type 1 according to GOST 27.003-90.
1.1.14 The law of distribution of uptime is exponential.
1.1.15 An example of recording the designation of a device when ordering it and in the documentation of other products is given in Table 1.......

Intended use
2.1 Preparing the Signal-VK1 device for use
Safety precautions when preparing the device
When operating the device, you must comply with the current “Rules for the technical operation of consumer electrical installations” and “Safety rules for the operation of consumer electrical installations.”
Sources of danger in the device are:
- contacts ХТ1:1 and ХТ1:3 for connecting the AC mains. Mounting, installation, and maintenance should be carried out when disconnected from
device mains voltage. Do not use fuses that do not correspond to the rated value. Installation and maintenance of the device must be carried out by persons with a safety qualification group of at least three.

ATsDR.425513.001 TU

Description:

The "Signal-VK-4P" device is designed for centralized and autonomous protection of closed heated and unheated premises (shops, banks, pharmacies, institutions, garages, hangars, warehouses and other premises) from unauthorized entry and fires by monitoring the status of four alarm loops ( ShS) and issuing notifications via four outputs to the monitoring station console.

Peculiarities:

  • Monitoring four loops allows you to replace a group of single-loop devices at a facility and organize multi-loop security.
  • Monitoring changes in the resistance of the security loop in the range from 2 to 11 kOhm at a rate of up to 10% in 1 hour relative to the current value.
  • Monitoring changes in fire alarm loop resistance in the range from 2 to 6 kOhm.
  • The device remains in standby mode in case of alarm loop violation in security mode for up to 50 ms and in fire loop mode for up to 250 ms.
  • Various operating modes of remote light and sound alarms depending on the activation of a security or fire alarm system.
  • Generation of a malfunction notification at the monitoring station 3 in the event of a malfunction of the fire alarm system.

The device provides:

  • Possibility of including current-consuming security and fire detectors such as “Window”, “Photon”, “Volna-5”, DIP and the like into the alarm loop;
  • Possibility of power supply to detectors such as “Echo”, Photon”, “Volna”, “Peak” and others;
  • Setting the “without the right to turn off” mode using jumpers to provide the “silent” alarm functions of the third alarm loop and the fire loop of the fourth alarm loop;
  • Setting the mode of switched-off sirens, signaling devices and indicators using a remote encryption device;
  • Setting a 30-second delay for turning on the siren after the device issues an alarm notification via ShS1;
  • Possibility of autonomous security when powered from an AC network with the issuance of signals to external light network, light and sound DC annunciators, built-in light indicators displaying the status of four ALs, and to a built-in sound alarm.

Device connection diagram:

A1- device "Signal VK-4P";
HL1- DC light indicator type "Mayak" (12 V);
R1…R3- resistor C2-33N-0.5-8.2 kOhm 5%;
R4- resistor C2-33N-0.5-8.2 kOhm 5% (in security mode);
R4- resistor S2-33N-0.5-4.7 kOhm 5% (in fire mode);
I1, I3, I5, I7- detectors with normally closed contacts;
I2, I4, I6, I8- detectors with normally open contacts or detectors such as “Window”, “DIP”, “Volna-5”, “Photon”.

Characteristics of the device "Signal-VK-4P":

Alarm loops:
quantity, pcs 4
maximum line resistance, kOhm 1
minimum line leakage resistance, kOhm 20
resistance of remote resistor in security mode, kOhm 8,2
resistance of remote resistor in fire mode, kOhm 4,7
"Alarm" notification to the monitoring station opening the contacts of the executive relays
Notification "Fire" at the monitoring station closing the contacts of the executive relays
Maximum switched contacts of executive relays:
current, mA
50
voltage, V 72
Power supply for detectors from the device:
voltage, V
10,8-13,2
current, mA 100
Power consumed from the AC network without a network siren, VA 30
Backup power supply of the device (from a DC source):
voltage, V
12-18
current (including power supply to detectors) in standby mode, mA 300
Duration of sounder operation, min 2
Maximum power of remote light network siren, VA 60
Maximum power of DC remote sounder 12Vx0.6A
Maximum power of remote DC warning light 12Vx0.05A
Operating temperature range, C from -30 to +50
Overall dimensions, mm 210x170x85
Weight, kg 2