Coordinate axes in drawings. Rules for the execution of architectural and construction drawings. Working drawings of architectural solutions

Coordinate axes in drawings.  Rules for the execution of architectural and construction drawings.  Working drawings of architectural solutions
Coordinate axes in drawings. Rules for the execution of architectural and construction drawings. Working drawings of architectural solutions

Construction drawings of buildings are carried out according to the general rules of rectangular projection onto the main projection planes. Views of a building from the front, back, right and left are called facades. On construction drawings, the name of the type is usually inscribed above its image, like “Facade 1–6”. The name of the facade indicates the extreme coordination axes. The top view of the building is called the roof plan. A horizontal section of a building is called a plan. The name of the plan refers to the floor, for example “1st Floor Plan”.
In construction drawings, it is allowed to use letters and numbers to name a section and include the word “section”, for example: “Section 1-1”. Image titles are not underlined.

according to GOST R 21.1101-2013:

5.5.1 Images in the drawings are made in accordance with GOST 2.305, taking into account the requirements of this standard and other SPDS standards.

5.5.3 If individual parts of the view (façade), plan, section require a more detailed image, then additionally local views and detailed elements - nodes and fragments - are performed.

5.5.4 On the image (plan, facade or section) from which the node is taken out, the corresponding place is marked with a closed solid thin line (circle, oval or rectangle with rounded corners) with the designation of the node in Arabic numeral on the shelf leader line in accordance with Figure 11 A, 11b or a capital letter of the Russian alphabet in accordance with Figure 11 V.

Figure 11

If necessary, references to a unit placed in another graphic document (for example, the main set of working drawings), or to working drawings of a typical construction unit, indicate the designation and sheet number of the corresponding document in accordance with Figure 11 b or a series of working drawings of typical units and issue number in accordance with Figure 11 V.

Figure 12

Above the image of the node its designation is indicated in a circle in accordance with Figure 13 A, if the node is depicted on the same sheet from which it was taken, or 13 b, if it is placed on another sheet.

Figure 13

A node that is a complete mirror image of another (main) design is assigned the same designation as the main design, with the addition of the index “n”.

5.5.5 Local species are designated in capital letters of the Russian alphabet, which are placed next to the arrow indicating the direction of view. The same designations are applied above the images of species.

5.5.6 For each type of images (sections and sections, nodes, fragments), an independent numbering order or letter designations are used.

5.5.7 On the image (plan, facade or section) from which the fragment is removed, the corresponding place is usually marked with a curly bracket in accordance with Figure 14.

Figure 14

The name and serial number of the fragment are placed under the curly bracket or on the shelf of the leader line, as well as above the corresponding fragment.

5.5.8 Images up to the axis of symmetry of symmetrical plans and facades of buildings and structures, layout diagrams of structural elements, layout plans for technological, energy, sanitary and other equipment are not allowed.

5.5.9 If the image of a section, section, node, view or fragment is placed on another sheet, then after the designation of the image indicate in brackets the number of this sheet in accordance with Figures 10, 11 A, 12 and 14.

5.5.10 Images may be rotated. At the same time, in the names of the images in the drawings, the conventional graphic designation “rotated” according to GOST 2.305 is not given if the position of the image is unambiguously determined, i.e. oriented by coordination axes and/or elevation marks.

5.5.11 If the image (for example, a plan) does not fit on a sheet of the accepted format, then it is divided into several sections, placing them on separate sheets.

In this case, on each sheet where a section of the image is shown, a diagram of the entire image is given with the necessary coordination axes and a symbol (hatching) of the section of the image shown on this sheet in accordance with Figure 15.

Note - If drawings of image sections are placed in different main sets of working drawings, then the full designation of the corresponding main set is indicated above the sheet number.

Figure 15

5.5.12 If the floor plans of a multi-story building have slight differences from each other, then the plan of one of the floors is completed in full; for other floors, only those parts of the plan that are necessary to show the difference from the plan depicted in full are carried out.

Under the name of the partially depicted plan, the following entry is given: “For the rest, see plan (name of the fully depicted plan).”

5.5.13 In the names of the plans of a building or structure, indicate the word “Plan” and the mark of the finished floor or the floor number, or the designation of the corresponding cutting plane (when two or more plans are made at different levels within the floor).

Examples

1 Plan at elevation. 0.000

2 2nd floor plan

When executing a part of a plan, the name indicates the axes that limit this part of the plan.

Example - Plan at elevation. 0.000 between axes 21-30 and A-D

It is allowed to indicate in the name of the floor plan the purpose of the premises located on the floor.

5.5.14 In the names of sections of a building (structure), the word “Section” and the designation of the corresponding cutting plane according to 5.5.2 are indicated.

Example - Cut 1-1

Note - In the names of product sections, the word “Cut” is not indicated.

The names of sections are numerical or alphabetic designations of cutting planes.

Example - 5-5, B-B, a-a

5.5.15 In the names of the facades of a building or structure, indicate the word “Facade” and the designations of the extreme axes between which the facade is located.

Example - Facade 1-12, Facade 1-1, Facade A-G

Size called the design size l building structure, product, element, element of equipment, determined in accordance with the rules of the ICRS (modular coordination of dimensions in construction). Structural dimensions (Fig. 109) take less than coordination dimensions l 0 per gap size d or more coordination dimensions (with the addition of the value of protrusions located in the adjacent coordination space). The gap size d is set in accordance with the characteristics of the structural units, operating conditions of the joints, installation and tolerances.

Nominal dimensions l 0 structural elements are the design dimensions of building products and equipment, including standardized clearances d; the normalized gap is the thickness of the gap seam established by the standards between structural elements.

Design dimensions l– design dimensions of structural elements, construction products and equipment.

Rice. 109. Location of building structures, products and elements in coordination space

Full size structural elements are their actual dimensions, which differ from the structural ones by the amount of tolerances established by the standards.

Features of applying dimensions on construction drawings. on construction drawings, dimensions are applied in accordance with GOST 2.307-68, taking into account the requirements of the design documentation system for construction GOST 21.501-93.

To determine the dimensions of the depicted product (structural element, unit, building, structure) and its parts, use the dimensional numbers printed on the drawing. Dimension and extension lines are drawn as a solid thin line with a thickness of S/3 to S/2 (see Fig. 109).

Dimensions in millimeters on construction drawings are usually applied in the form of a closed chain without indicating the unit of measurement. If dimensions are given in other units, this is specified in the notes to the drawings. Dimension lines on construction drawings are limited by serifs - short strokes 2-4 mm long, drawn with an inclination to the right at an angle of 45° to the dimension line. The thickness of the notch line is equal to the thickness of the solid main line adopted in this drawing. Dimension lines should protrude beyond the outer extension lines by 1-3 mm. The size number is placed above the size line at approximately a distance of 0.5 to 1 mm (Fig. 110a, 110b). The extension line should extend beyond the dimension line by 1-5 mm. If there is not enough space for serifs on dimension lines, which are a closed chain, serifs can be replaced with dots (Fig. 110c).

Rice. 110. Limitation of dimension lines

The distance from the outline of the drawing to the first dimension line is recommended to be at least 10 mm. However, in the practice of design work, this distance is taken to be 14-21 mm. The distance between parallel dimension lines must be at least 7 mm, and from the dimension line to the circle of the coordination axis - 4 mm (Fig. 111).

Rice. 111. Example of applying dimensions on an image with a gap
with one dimension line

If there are a number of identical elements in the image, located at equal distances from each other (for example, the axes of columns), the dimensions between them are indicated only at the beginning and end of the row (Fig. 112) and indicate the total size between the extreme elements in the form of the product of the number of repetitions by repeating size.

The dimension line on construction drawings is limited by arrows in accordance with GOST 2.307-68 if it is necessary to indicate the diameter, radius of a circle or angle, as well as when drawing dimensions from a common base located on a common dimension line (Fig. 113b and Fig. 114)

Rice. 112. Example of applying dimensions on an image with a gap
with several dimension lines

Rice. 114. Size line

6.6. Building plan

Plan is an image of a section of a building, dissected by an imaginary horizontal plane passing at a certain level, as shown in Fig. 115.

According to GOST 21.501–93, this plane should be located at 1/3 of the height of the depicted floor. For residential and public buildings, an imaginary cutting plane is located within the door and window openings of the floor.

The building plan drawing shows what falls on the cutting plane and what is located under it. Thus, the plan of a building is its horizontal section.

The building plan gives an idea of ​​the shape of the building in plan and the relative position of individual rooms. The building plan shows window and door openings, the location of partitions and main walls, built-in cabinets, sanitary equipment, etc. Sanitary equipment is drawn on the building plan on the same scale as the building plan.

If the plan, facade and section of the building are placed on one sheet, then the plan is placed under the facade in projection connection with it. However, due to the large size of the images, plans are usually placed on separate sheets, with their long side located along the sheet.

When starting to draw a plan, you should remember that it is recommended to turn the side of the plan corresponding to the main facade of the building towards the bottom edge of the sheet. When determining the place on the sheet for the building plan drawing, you should take into account the applied dimensions and marking of the coordination axes. Therefore, the plan drawing should be located approximately 75 - 80 mm from the sheet frame. In specific cases, these dimensions may vary. After determining the location of the plan on the sheet and its scale, they begin drawing.

1. Draw a dash-dotted line 0.3...0.4 mm thick with the coordinate axes of the plan, longitudinal and transverse, as shown in Fig. 116. These axes serve to link the building to the construction coordinate grid, as well as to determine the position of load-bearing structures, since these axes are drawn only along main walls and columns.

To mark axes on the side of a building with a large number of them, Arabic numerals 1, 2, 3, etc. are used. Most often, a larger number of axes run across the building. To mark the axes on the side of the building with fewer of them, use the letters of the Russian alphabet A, B, C, etc. As a rule, axes running along the building are marked with letters. When marking axes, it is not recommended to use the letters: З, И, О, ​​Х, Ц, Ш, Ш, И, ь, Ъ. The axes are marked from left to right and from bottom to top. Gaps in serial numbering and alphabet when designating coordination axes are not allowed. Typically, marking circles (their diameter is 6....12 mm) are located on the left and bottom sides of the building. Removing the marking circle from the last 4 mm dimension line (see Fig. 112)


2. Taking into account the alignment of the axes according to the ICRS and the thickness of the walls, draw the contours of the longitudinal and transverse external and internal walls with thin lines (Fig. 117).


Capital walls are tied to coordination axes, i.e. determine the distances from the inner and outer planes of the wall to the coordination axis of the building, and the axis can not be drawn along the entire length of the wall, but drawn only by the amount necessary to set the reference dimensions. Coordination axes do not always have to coincide with the geometric axes of the walls. Their position should be set taking into account the coordination dimensions and the standard span structures of beams, trusses or floor slabs used. In buildings with load-bearing longitudinal and transverse walls, the binding is carried out in accordance with the following instructions.

In external load-bearing walls, the coordination axis passes from the internal plane of the walls at a distance equal to half the nominal thickness of the internal load-bearing wall, a multiple of the module or its half. In brick walls, this distance is most often taken equal to 200 mm, or equal to the module, i.e. 100 mm (Fig. 118a). In external self-supporting walls, if the floor panels do not fit into it, for the convenience of calculating the number of standard floor elements, the coordination axis is aligned with the inner edge of the wall, which is called zero reference (Fig. 118b). If the floor elements rest on the outer wall along its entire thickness, the coordination axis is aligned with the outer edge of the wall (Fig. 118c). In the internal walls, the geometric axis of symmetry is combined with the coordination axis (Fig. 118d). Deviations from this rule are allowed for the walls of staircases and walls with ventilation ducts.

Draw the contours of the partitions with two thin lines (Fig. 117). Partitions are tied to marking axes depending on the layout of the premises in the building.

It is necessary to pay attention to the difference in the connection of external and internal main walls and main walls and partitions. If the material of the walls being connected is the same, then the walls are drawn as one whole. If the material of the walls is different, then they are drawn as different elements.

3. At this stage, flights of stairs are depicted and window and door openings are broken down (Fig. 119).

When drawing flights of stairs, the gap between flights should be selected within the range of 100–200 mm, and the width of the treads should be 300 mm.

The symbol for window and door openings with and without filling is shown in accordance with GOST 21.501–93. When drawing a plan on a scale of 1:50 or 1:100, if there are quarters in the openings, their conventional image is given in the drawing. It should be borne in mind that the dimensions of the openings are indicated in GOST without taking into account the quarters, so in the drawings the dimensions are indicated minus the quarters, i.e. 130mm is subtracted from the opening size.

It should be remembered that when drawing the partition delimiting the vestibule of the entrance, it must be applied after drawing the ribbon marches. This is due to the fact that the dimensions of the vestibule are limited by the dimensions of the interfloor area. The width of the doorway in this partition is similar to the width of the entrance opening without taking into account the quarter (see Fig. 119, 122).

Quarter - this is a protrusion in the upper and side parts of the openings of brick walls, which reduces airflow and facilitates the fastening of boxes (Fig. 120). In Fig. Figure 120a shows window openings with and without a quarter, and Figure 120b shows doorways with and without a quarter.

It should be noted that when depicting windows on plans and sections on a scale of M1:100 and M1:50 glazing in window openings with a quarter, the first glazing thread is shown along the quarter, and the second 1 mm into the building from the first.

Door widths can be selected from the following range: 700 mm for bathrooms and toilets; 800 mm or 900 mm for rooms and kitchens; 900 mm or 1000 mm – entrance doors to the apartment; 1200 mm or 1500 mm (double-leaf) – entrance doors to the entrance. When placing a doorway in the wall for interior doors, one must take into account the ease of use of the premises, the intended arrangement of furniture, etc., which should be taken into account when determining the direction of opening the doors.

Some recommendations for the placement of doors: doors to living rooms and kitchens should open into the room; doors leading to the bathroom and toilet open outwards; doors should clutter the room as little as possible.

On the plans, the door leaves are shown as a solid thin line and open at approximately an angle of 30º (the angle is not indicated in the drawing). The entrance doors to the building only open outwards.

4. After the windows and doors are shown, the location of the plumbing equipment is shown (Fig. 119): in the kitchen - sink and stove, in the toilet - toilet, in the bathroom - bathtub and washbasin. Conventional graphic images of plumbing equipment are performed in accordance with GOST 2.786-70* and GOST 21.205-93, the dimensions of the most common plumbing equipment are given in Fig. 121.

5. Outline the contours of partitions and main walls with lines of appropriate thickness, mark the dimensions and areas of the premises, as shown in Fig. 122. When choosing the thickness of the outline lines, it should be taken into account that non-load-bearing structures, in particular the contours of partitions, are outlined with lines of less thickness than load-bearing main walls.

Dimensions marked outside the building plan. The first dimension line (chain) with alternating dimensions of the walls and openings is drawn at a distance of 15....20 mm from the external contour of the plan.

The second dimensional chain indicates the distances between adjacent coordination axes.

On the third dimensional chain, the distance between the extreme coordination axes is indicated.

The distance between parallel dimension lines (chains) must be at least 7 mm, and from the dimension line to the marking circle of the coordination axis - 4 mm. Circles to indicate coordination axes are taken with a diameter of 6....12 mm.

The dimensions for linking the external walls to the coordination axes are placed before the first dimensional chain.

Horizontal traces of imaginary secant planes of the section are also applied on the plans, which are then used to construct images of sections of the building. These marks are thick open strokes 1mm thick with arrows as shown in Fig. 122. If necessary, the imaginary plane of the section can be depicted with a thick dash-dotted line. The direction of the arrows, i.e. The direction of view is recommended to be taken from bottom to top or from right to left. However, if necessary, you can choose another direction. Depending on the position of the dimensional chains and the workload of the drawing, they can be located near the outline of the plan or behind the outermost dimensional chain as shown in Fig. 122. Cutting planes of sections are designated by letters of the Russian alphabet or numbers.

Dimensions included inside the building plan. The internal dimensions of premises (rooms), the thickness of partitions, internal walls, the dimensions of doorways are marked on internal dimensional lines (chains). Internal dimension lines are drawn at a distance of at least 8...10 mm from the wall or partition.

Indicate the width and length of the staircase, the coordination dimensions of the width of the landings, and the length of the horizontal projection of the flights.

The area size figure, accurate to 0.01 m2, is placed on the plan in a free space, closer to the lower right corner of each room, underlining it with a solid main line.

The height of the floor and interfloor platforms, and for the first floor - the entrance platform, is indicated in a rectangle accurate to the third significant digit after the decimal point, indicating the “+” or “-” sign.

An inscription is made above the plan drawing. For industrial buildings, this will be an indication of the floor level of the production room or site according to the type “Plan at elevation. +2,500.” The word “mark” is written in abbreviation. For civil buildings, you can write the name of the floor in the inscription using the “1st floor plan” type. The inscriptions are not underlined.

The name of the premises is indicated on the plan. If the size of the image does not allow making an inscription on the drawing, then the rooms are numbered and their names are given in the legend. Marking numbers are placed in circles with a diameter of 6–8 mm.

Drawings of floor plans are accompanied by an explication of the premises; statements of finishing of premises, etc. The shapes and sizes of legends and statements are shown in Fig. 123.


● contours of load-bearing walls falling within a section of 0.6 – 0.7 mm;

● contours of partitions 0.3 – 0.4 mm;

● contours of elements not included in the section, images of stairs, plumbing equipment 0.3 mm;

● thickness of extension, dimension, center lines, marking circles and other auxiliary lines is 0.2 mm.

6.7. Control questions

1. What drawings are called construction drawings?

2. List the types of buildings according to their purpose.

3. What is the brand of the main set of working drawings of architectural solutions.

4. What is called a structural element?

5. List the main structural elements of the building.

6. What is a module? What are the meanings of enlarged modules?

7. How are coordination axes designated?

8. Features of applying dimensions on construction drawings.

8. What is called a floor plan?

9. What scales of construction drawings are used to draw plans for residential buildings?

10. How is a plan designated?

11. What is the sequence of the floor plan?

12. How are the mills attached to the marking axes?

13. What is the conventional image in plan of a window opening with and without quarters?

14. What is the conventional image in plan of a doorway with and without quarters?

15. How are elements of plumbing equipment depicted on the plans?

16. What dimensions are shown on the floor plan?

17. How are the areas of premises indicated on the plans?

18. How and what lines are used when outlining a floor plan.

19. What thickness of lines is used when constructing a plan?

Lecture 7. CUT

7.1. Markings of levels of structural elements.

7.2. General information about sections of buildings.

7.3. Methodology for constructing a vertical section of a building.

7.4. Construction of floors.

7.5. Construction of window and door openings.

7.5. Control questions.

7.1. Structural element level marks

Marks. Conventional level marks (heights, depths) on plans, sections, facades show the height distance from the surface level of any building structural element located near the planning surface of the ground. This level is taken as zero.

Markings of height levels and depths of structural elements from the reference level (the conventional “zero” mark) are indicated in meters with three decimal places separated from the whole number by a comma. On facades, sections and sections, marks are placed on the extension lines of the contour.

The conditional “zero” mark is indicated without the sign “ 0,000 » or with the sign "±0.000"(recommended to be marked with the sign "±"); marks above zero – with a “+” sign; below zero – with a “–” sign.

On views (elements), sections and sections, marks are placed on extension lines or contour lines and indicated with a symbol. The marking sign is (GOST 21.105 – 79) an arrow with a shelf. In this case, the arrow is made with main lines 2-4 mm long, drawn at an angle of 45° to the extension line or contour line. A vertical or horizontal leader line is outlined with a solid thin line (Fig. 124a, 124b).

If necessary, the height and length of the shelf can be increased. If several level signs are located one above the other near one image, it is recommended to place the vertical lines of the mark on the same vertical straight line, and make the length of the horizontal shelf the same (Fig. 124c).

The marking sign may be accompanied by explanatory notes. For example: " Ur.ch.p." – finished floor level; " Lv.z." – ground level (Fig. 124d).

On construction drawings, level marks in sections (Fig. 125a), facades (Fig. 125b) and plans (Fig. 125c) are indicated in meters with three decimal places separated from the whole number by a comma.

The conditional zero mark is designated as follows: 0.000. A dimensional number showing the level of an element located below the zero mark has a minus sign (for example -1.200), and one located above has a plus sign (for example +2.700).

On plans, the dimensional number is marked in a rectangle, the contour of which is outlined by a thin solid line, or on the shelf of a leader line. In this case, a plus or minus sign is also placed in front of the dimensional number (Fig. 125c).

7.2. General information about building sections

By cut called the image of a building mentally dissected by a vertical plane, Fig. 126. If the plane is perpendicular to the longitudinal axes, then the cut is called transverse, and parallel to them - longitudinal. Sections on construction drawings serve to identify the volumetric and structural design of the building, the relative position of individual structures, rooms, etc.

Sections can be architectural or structural.

Architectural sections serve to identify the internal appearance of premises and the location of architectural elements of the interior, which do not show the structures of floors, rafters, foundations and other elements, but indicate the height of the premises, window and door openings, basement, etc. The heights of these elements are most often determined by elevation marks. Architectural sections are drawn up at the initial design stage to develop the façade of the building. An architectural section is not used for the construction of a building, since it does not show the structural elements of the building, Fig. 127.

Construction cuts carried out at the stage of developing working drawings of the building, which show the structural elements of the building (foundations, rafters, floors), and also apply the necessary dimensions and marks, Fig. 128.

In working drawings, the direction of view for sections is taken, as a rule, according to the plan - from bottom to top and from right to left. Sometimes, if necessary or for educational purposes, the direction of gaze is taken from left to right.

The position of the cutting plane is chosen such that it passes through the most structurally or architecturally important parts of the building: window and door openings, staircases, balconies, etc. It should be borne in mind that the plane of the cut along the stairs is always drawn along the flights closest to the observer. In this case, the flight of stairs that falls into the cut is outlined with a line of greater thickness (solid main) than the outline of the flight along which the cutting plane does not pass. The outline of this march is outlined with a solid thin line.

The construction of the main elements of buildings is carried out using modular coordination of dimensions in construction (MDCS), according to which the dimensions of the main space-planning elements of the building must be a multiple of the module.
The main module is assumed to be 100 mm.
The main structural elements (load-bearing walls, columns) of the building are located along the modular coordination axes(longitudinal and transverse). The distance between coordination axes in low-rise buildings is taken as multiples of the 3M module (300 mm).
To determine the relative position of building elements, it is used grid of coordination axes.
Coordination axes are drawn with dash-dot thin lines and are indicated, as a rule, on the left and lower sides of the plan, marked, starting from the lower left corner, with Arabic numerals (from left to right) and capital letters of the Russian alphabet (from bottom to top) in circles with a diameter of 6 ... 12 mm (Fig. .2).

Rice. 2. Example of marking of coordination axes


Dimensions on construction drawings they are indicated in millimeters and are applied, as a rule, in the form of a closed chain.
Dimension lines are limited by serifs - short strokes 2 ... 4 mm long, drawn with an inclination to the right at an angle of 45° to the dimension line. Dimension lines should protrude beyond the outer extension lines by 1 ... 3 mm. The dimension number is located above the dimension line at a distance of 1 ... 2 mm (Fig. 3, a).
To indicate cutting plane position For a section or cross-section of a building, an open line is used in the form of separate thickened strokes with arrows indicating the direction of view. The cut line is indicated in Arabic numerals (Fig. 3, c). The starting and ending strokes should not cross the outline of the image.
The height dimensions of buildings (floor heights) are assigned as multiples of modules. Floor height of a building is defined as the distance from the floor level of a given floor to the floor level of the floor above it. In residential building projects, the floor height is assumed to be 2.8; 3.0; 3.3 m.
High-rise drawings are applied on facades and sections. marks level of an element or structure of a building from any design level taken as zero. Most often, the level of the finished floor (floor covering) of the first floor is taken as the zero level (mark ±0.000).
Level marks are indicated in meters with three decimal places without indicating units of length and are placed on extension lines in the form of an arrow with a shelf. The sides of the right angle of the arrow are drawn as a solid thick main line at an angle of 45° to the extension line (Fig. 4).



Rice. 3. Drawing the dimensions and positions of the cuts:


a – dimensions and dimension lines; b – view direction arrow;
c – positions of the cuts




Rice. 4. Applying level marks on views:


a – dimensions of the level mark; b – examples of location and design
level signs on sections and sections; c – the same, with explanatory inscriptions;
d – example of a level sign on the plans

The marking sign may be accompanied by explanatory inscriptions: Ur.ch.p. – finished floor level; Ur.z. - ground level.
Marks on the plans are made in rectangles (Fig. 4, d). Marks above the zero level are indicated with a plus sign (for example, + 2.700), below zero - with a minus sign (for example, – 0.200).
The following are accepted in the construction drawings: names types of buildings.
IN names of plans of the building, the level of the finished floor of the floor, the floor number or the designation of the corresponding plane is indicated; when executing part of the plan - the axes limiting this part, for example:
Plan at elevation +3,000;
2nd floor plan;
Plan 3–3;
Plan at elevation 0.000 in axes 21–39, A–D.
IN names of sections building, the designation of the corresponding cutting plane is indicated (in Arabic numerals), for example, Section 1–1.
IN names of facades building, the extreme axes between which the façade is located are indicated, for example:
Façade 1–5;
Façade 12–1;
Façade A–G.
For multilayer structures callouts, located on shelves in a straight line,
ending with an arrow (Fig. 5). The sequence of inscriptions (material or design of layers indicating their thickness) for individual layers must correspond to the sequence of their location in the drawing from top to bottom and from left to right.
On leader lines, ending with a shelf, additional explanations to the drawing or item numbers of elements in the specification are placed.



Rice. 5. Examples of callouts

Graphic symbols materials in sections and sections of buildings and structures are given in the appendix. 3. The distance between parallel hatching lines is selected within 1 ... 10 mm depending on the hatching area and image scale. Designations of materials are not used in drawings if the material is homogeneous, if the dimensions of the image do not allow the application of a symbol.
Conventional graphic images of building elements and sanitary installations are given in the appendix. 4.

Appendix 3


GRAPHIC DESIGNATION OF MATERIALS IN SECTIONS,
SECTIONS AND TYPES




Appendix 4


GRAPHIC REPRESENTATIONS OF BUILDING ELEMENTS


Categories: / /
Tags:

Coordination axes are applied to images of buildings and structures with thin dash-dotted lines with long strokes, denoted by Arabic numerals and capital letters of the Russian alphabet (with the exception of the letters: Е, З, И, О, b) in circles with a diameter of 6–12 mm.

Gaps in digital and alphabetic (except for those indicated) designations of coordination axes are not allowed.

The numbers indicate the coordination axes on the side of the building and structure with a large number of axes. If there are not enough letters of the alphabet to designate the coordination axes, subsequent axes are designated by two letters.

Example - AA; BB; BB.

The sequence of digital and letter designations of the coordination axes is taken according to the plan from left to right and from bottom to top (Figure 10 A) or as shown in figures 10 b,V.

The designation of coordination axes, as a rule, is applied on the left and lower sides of the plan of the building and structure.

If the coordination axes of opposite sides of the plan do not coincide, the designations of these axes in the places of discrepancy are additionally applied on the top and/or right sides.

For individual elements located between the coordination axes of the main load-bearing structures, additional axes are drawn and designated as a fraction:

The designation of the previous coordination axis is indicated above the line;

Below the line is an additional serial number within the area between adjacent coordination axes in accordance with Figure 10 G.

It is allowed to assign numerical and letter designations to the coordination axes of half-timbered columns in continuation of the designations of the axes of the main columns without an additional number.

Figure 10 – Designations of coordination axes

In the image of a repeating element tied to several coordination axes, the coordination axes are designated in accordance with Figure 11:

- “a” - when the number of coordination axes is no more than 3;

- “b” - “ “ “ “ more than 3;

- “in” - for all letter and digital coordination axes.

If necessary, the orientation of the coordination axis to which the element is attached, in relation to the adjacent axis, is indicated in accordance with Figure 11 G.


Figure 11 – Orientation of coordination axes

To designate the coordination axes of block sections of residential buildings, the index “c” is used.

Example - 1s, 2s, Ac, Bs.

On the plans of residential buildings composed of block sections, the designations of the extreme coordination axes of the block sections are indicated without an index in accordance with Figure 12.

Figure 12 – Designation of coordination axes

in block sections

        Applying dimensions, slopes, marks, inscriptions. Linear dimensions and maximum deviations of linear dimensions in the drawings are indicated in millimeters, without indicating the unit of measurement.

The dimension line at its intersection with extension lines, contour lines or center lines is limited by serifs in the form of thick main lines 2–4 mm long, drawn with an inclination to the right at an angle of 45° to the dimension line by 1–3 mm.

When applying a diameter or radius dimension inside a circle, as well as an angular dimension, the dimension line is limited by arrows. Arrows are also used when drawing dimensions of radii and internal fillets.

When applying the size of a straight segment, the dimension line is drawn parallel to this segment, and extension lines – perpendicular to the dimension lines.

It is preferable to apply dimensions outside the outline of the image, avoiding, if possible, intersections of extension and dimension lines. If it is necessary to apply a dimension in a shaded area, the corresponding dimension number is placed on the shelf of the leader line.

The minimum distance between parallel dimension lines should be 7 mm, and between the dimension line and the contour line - 10 mm and is selected depending on the size and shape of the image, as well as the saturation of the drawing.

Dimensional numbers are applied above the dimension line, as close as possible to its middle.

Level marks (heights, depths) of structural elements, equipment, pipelines, air ducts, etc. from the reference level (the conventional “zero” mark) are indicated by a conventional sign in accordance with Figure 13 and are indicated in meters with three decimal places, separated from the whole number by a comma.

Figure 13 – Level mark designation

The “zero” mark, usually accepted for the surface of any structural element of a building or structure located near the planning surface of the earth, is indicated without a sign; marks above zero - with a “+” sign; below zero - with a “-” sign.

On views (elements), sections and sections, marks are indicated on extension lines or contour lines in accordance with Figure 14, on plans - in a rectangle in accordance with Figure 15.

Figure 14 – Indication of level marks on sections

Figure 15 – Indicating marks on plans

On the plans, the direction of the slope of the planes is indicated by an arrow, above which, if necessary, the value of the slope is indicated as a percentage in accordance with Figure 16 or as a ratio of height and length (for example, 1:7).

It is allowed, if necessary, to indicate the slope value in ppm, as a decimal fraction accurate to the third digit. On drawings and diagrams, in front of the dimensional number that determines the magnitude of the slope, the sign “Д is applied, the acute angle of which must be directed towards the slope.

The slope designation is applied directly above the contour line or on the shelf of the leader line.

Figure 16 - Indicating the direction and magnitude of the plane slope

Near the images on the shelves of leader lines, only short inscriptions are applied directly to the image of the object, for example, indications of the number of structural elements (holes, grooves, etc.), if they are not included in the table, as well as indications of the front side, direction rolled products, fibers, etc.

A leader line that intersects the contour of the image and does not depart from any line ends with a dot (Figure 17 A).

The leader line, drawn from the lines of the visible and invisible contour, as well as from the lines indicating surfaces, ends with an arrow (Figure 17 b,V).


Figure 17 – Drawing leader lines

Labels for multilayer structures should be made in accordance with Figure 18.


Figure 18 – Labeling multilayer structures

Position numbers (brands of elements) are placed on the shelves of leader lines drawn from images of the component parts of the object, next to the image without a leader line or within the contours of the depicted parts of the object in accordance with Figure 19.

In small-scale images, leader lines end without an arrow or a dot.

Figure 19 – Drawing the positions of the elements of objects

Leader lines should not intersect each other, be non-parallel to the hatch lines (if the leader line runs along a shaded field) and, if possible, not intersect dimension lines and image elements that do not include the inscription placed on the shelf.

It is allowed to make leader lines with one break (Figure 20), as well as draw two or more leader lines from one shelf (Figure 21).


Inscriptions related directly to the image can contain no more than two lines, located above and below the leader line shelf.

The font size for indicating coordination axes and positions (marks) should be one to two numbers larger than the font size adopted for dimensional numbers in the same drawing.

The text part placed on the drawing field is placed above the main inscription.

It is not allowed to place images, tables, etc. between the text part and the main inscription.

On sheets larger than A1, text may be placed in two or more columns. The column width should be no more than 185 mm.

Tables are placed in the free space of the drawing field to the right of the image or below it.

Tables placed on the drawing are numbered within the drawing if there are references to them in the technical requirements. In this case, the word “Table” with a serial number (without the No. sign) is placed above the table on the right.

If there is only one table in the drawing, then it is not numbered and the word “Table” is not written.

When making a drawing on two or more sheets, the text part is placed only on the first sheet, regardless of which sheets contain the images to which the instructions given in the text part relate.

Inscriptions relating to individual elements of an object and placed on the shelves of leader lines are placed on those sheets of the drawing on which they are most necessary for ease of reading the drawing.

The inscriptions on the drawings are not underlined.

To designate images (types, sections, sections), surfaces, dimensions and other elements of the product in the drawing, capital letters of the Russian alphabet are used, with the exception of the letters Y, O, X, Ъ, ы, ь.

Letter designations are assigned in alphabetical order without repetition and, as a rule, without gaps, regardless of the number of sheets of the drawing. It is preferable to label the images first.

In case of a lack of letters, numerical indexing is used, for example: “Type A”; "View A 1"; "View A 2"; "B-B"; "B 1 -B 1"; "B 2 -B 2". Letter designations are underlined.

If symbols are applied by machine, they may not be underlined.

The font size of the letter designations should be approximately twice the size of the digits of the dimensional numbers used in the same drawing.

The scale of the image in the drawing, which differs from that indicated in the main inscription, is indicated directly under the inscription related to the image, for example:


If in a drawing it is difficult to find additional images (sections, dimensions, additional views, extension elements) due to the large saturation of the drawing or its execution on two or more sheets, then additional images are marked indicating the sheet numbers or designations of the zones on which these images are placed (Figure 22).

Figure 22 – Indication of sheet numbers in addition to the image

In these cases, above the additional images, their designations indicate the sheet numbers or designations of the zones on which the additional images are marked (Figure 23).

Figure 23 – Making inscriptions on additional images

A building or any structure in plan is divided by conventional center lines into a number of segments. These lines defining the position of the main load-bearing structures are called longitudinal and transverse coordination axes.

The interval between the coordination axes in the building plan is called the step, and in the predominant direction the step can be longitudinal or transverse.

Marking of coordination axes

If the distance between the coordinate longitudinal axes coincides with the span, floor or coating of the main supporting structure, then this interval is called a span.

Floor height in a multi-storey residential building

The height of the floor H fl is taken to be the distance from the floor level of the selected floor to the floor level of the floor above. The height of the upper floor is determined using the same principle, whereby the thickness of the attic floor is assumed to be conditionally equal to the thickness of the interfloor floor c. In industrial one-story buildings, the height of the floor is equal to the distance from the floor to the bottom surface of the coating structure.

In order to determine the relative position of parts of a building, a grid of coordination axes is used, which defines the load-bearing structures of a given building.

Coordination axes are dashed with thin dotted lines and marked inside circles with a diameter of 6 to 12 mm.

Floor height in a one-story building

Coordination axes are marked in Arabic numerals and capital letters, with the exception of the symbols: 3, И, О, ​​X, И, ъ, ь.

The height of the font indicating the coordination axes is chosen to be one or two numbers larger than the size of the numbers on the same sheet.

The numbers indicate the axes on the side of the building with the largest number of coordination axes.

The direction of marking of axes is applied from left to right, horizontally and from bottom to top, vertically.

Axes markings are usually located on the left and bottom sides of the building plan.

The coordination axis of the outer wall is located at a distance a = 100 mm, observing the indentation for installing floor slabs.

Coordination axes of external and internal walls

  • 1 – Foundations and blocks; 2 – foundations; 3 – columns of the outermost row; 4 – columns of the middle row; 5 – crane beams; 6 – roof beams; 7 – coating slabs;
  • 8 – Drain funnel; 9 – insulation and roofing; 10 – parapet; 11 – wall panels;
  • 12 – Window frames; 13 – floor; 14 – lantern; 15 – roof trusses
  • Brands of main sets of working drawings (selection from GOST R 21.1101-2009)
  • The letters a, b, c indicate the longitudinal coordination axes;
  • The numbers 1, 2, 3, 4 indicate the transverse coordination axes
  • 1) Middle column; 2) crane beam; 3) floor slabs;
  • 4) Wall panel; 5) rafter beam; 6) wall column
  • A) in the middle rows; b-d) in the outer rows; e) at the ends; g-i) in places of height difference, expansion and expansion joints (on paired columns)
  • 3.1. Conventional graphic images on drawings of buildings and engineering systems
  • Representation of sanitary installations on plans
  • A) grid of coordination axes; b) attaching walls, marking partitions; c) drawing details; d) sizing and design
  • A) drawing the axes and contours of the building; b, c) marking and drawing details of the facade; d) sizing and design
  • A) drawing axes and horizontal levels; b) image of the contours of the main structural elements of the building; c) drawing details of the building’s interior; d) sizing and design
  • Different floors on the plan: a) staircase in section; b, c, d) plans of stairs on different floors


  • d) e)

    Fig.7.Options for drawing coordination axes

    are marked with letters from the center to the periphery and numbers - from the left horizontal axis clockwise (Fig. 7 a,7c). Axes are usually marked on the bottom and left sides of the building plan. If the axes of the opposite sides of the building do not coincide, then they are marked on each side accordingly (Fig. 7g

    ). For any elements For structures located between the coordination axes of the main load-bearing structures (for example, columns in a building diagram with an incomplete frame), additional axes are applied. These axes are designated by a fraction: the numerator indicates the designation of the previous coordination axis, and the denominator indicates an additional serial number within the area between adjacent coordination axes (Fig.

    7d

    ). It is allowed not to assign additional numbers to the axes of half-timbered columns, but to designate them in continuation of the designation of the axes of the main columns. 2.3. Snap walls to coordination axes In building drawings, the role of a coordinate grid is played by the coordination axes of the main walls. After drawing the coordination axes on the plan, perform

    binding


    to them structural elements, primarily external and internal load-bearing walls and supports. The binding is carried out by setting dimensions from the axis to both faces of the wall or column. In this case, the axis of the wall is not drawn along its entire length, but is extended only by the amount necessary to set the reference size. It is customary to draw the axes of supporting columns with two mutually perpendicular segments of dash-dotted lines.Coordination axes do not always coincide with the geometric axes of the walls. Their position is set taking into account the dimensions of standard span structures of beams, trusses and floor slabs. In the example in Fig. For clarity, Figure 8 partially shows the layout of the floor panels and their support on the walls. The panels are drawn in rectangles with thin diagonals.

    Fig.8.

      Links of main walls on the building plan

    Linking walls to modular coordination axes in buildings with load-bearing longitudinal or transverse walls is carried out based on the following instructions: A on internal walls, their geometric axis, as a rule, corresponds

      fits with the coordination axis (Fig. 9,

    ; rice. 8, axis B, axis 3);

    it is allowed not to combine geometric and coordination b axes of staircase walls, walls with ventilation ducts, etc.; in the walls of staircases, the axes are drawn at a distance that is a multiple of the module from the inner (facing the stairs) face of the wall (Fig. 9,);

      ; rice. 8,

    axis 2

    in external load-bearing walls the coordination axis is drawn fromOptions for anchoring load-bearing walls

    the internal (facing the room) edge of the wall at a distance equal to half the thickness of the corresponding internal load-bearing wall (Fig. 9, V axes of staircase walls, walls with ventilation ducts, etc.; A-axis, B axis, axis 4);

      in external self-supporting walls the so-called

    zero binding – the coordination axis is aligned with the internal

    the edge of the wall - (Fig. 9, G axes of staircase walls, walls with ventilation ducts, etc.; axis 1);

      if the outer wall is load-bearing in different sections

    cabbage soup ( section of wall along axis A between axes 1 and 3) and self-supporting ( section of wall along axis A between axes 3 and 4), then the coordination axis is oriented along the load-bearing section (Fig. 8);

      the binding of columns and walls of industrial buildings depends on their

    position in one of the rows (middle, extreme or end); Variants of such bindings are shown in Fig. 10.

    A) b) V)

    G) d) e)

    and) h) And)

    Fig. 10.Attaching columns to coordination axes:

  • GOST 21.101-97
    INTERSTATE STANDARD
    SYSTEM OF DESIGN DOCUMENTS FOR CONSTRUCTION
    BASIC REQUIREMENTS FOR DESIGN AND WORK DOCUMENTATION

    5. GENERAL RULES FOR COMPLETING DOCUMENTATION

    Coordination axes


    5.4. In the image of each building or structure, the coordination axes are indicated and an independent notation system is assigned to them.

    Coordination axes are applied to images of buildings and structures with thin dash-dot lines with long strokes, denoted by Arabic numerals and capital letters of the Russian alphabet (with the exception of the letters: Ё, 3, И, О, ​​X, Ц, Ш, Ш, ъ, ы, ь) in circles with a diameter of 6-12 mm.

    Gaps in digital and alphabetic (except for those indicated) designations of coordination axes are not allowed.

    5.5. The numbers indicate the coordination axes on the side of the building and structure with a large number of axes. If there are not enough letters of the alphabet to designate the coordination axes, subsequent axes are designated by two letters.
    Example: AA; BB; BB.

    5.6. The sequence of digital and letter designations of the coordination axes is taken according to the plan from left to right and from bottom to top (Fig. 1a) or as shown in Fig. 1b, c.

    5.7. The designation of coordination axes, as a rule, is applied on the left and lower sides of the plan of the building and structure.
    If the coordination axes of opposite sides of the plan do not coincide, the designations of the indicated axes in the places of discrepancy are additionally applied on the top and/or right sides.

    5.8. For individual elements located between the coordination axes of the main load-bearing structures, additional axes are drawn and designated as a fraction:
    above the line indicate the designation of the previous coordination axis;
    below the line is an additional serial number within the area between adjacent coordination axes in accordance with Fig. 1 year

    It is allowed to assign numerical and letter designations to the coordination axes of half-timbered columns in continuation of the designations of the axes of the main columns without an additional number.

    5.9. In the image of a repeating element attached to several coordination axes, the coordination axes are designated in accordance with Fig. 2:

    “a” - when the number of coordination axes is no more than 3;
    “b” - when the number of coordination axes is more than 3;
    “in” - for all letter and digital coordination axes.

    If necessary, the orientation of the coordination axis to which the element is attached in relation to the adjacent axis is indicated in accordance with Fig. 2g.


    Rice. 2

    5.10. To designate the coordination axes of block sections of residential buildings, the index “c” is used.
    Examples: 1s, 2s, Ac, Bs.

    On the plans of residential buildings composed of block sections, the designations of the extreme coordination axes of the block sections are indicated without an index in accordance with Fig. 3.


    Rice. 3