The comfortable life of modern people is almost unimaginable, especially in the hot season, without the presence of various types of air conditioners in residential, office and industrial premises. Failure of a split system in the hot summer, and if it is used for heating the room, also in winter, is a big problem that requires an immediate solution.

In this regard, residents of Moscow are very lucky, having the opportunity to use the services of technicians from the ETekhnik service center, who identify air conditioner malfunctions right at their clients’ homes and fix them. Although modern split systems are capable of self-diagnosis, and therefore, focusing on the error codes of air conditioners, or rather on their decoding, since it is unlikely that an ordinary person knows what an eeprom error is, you can independently find out what specific malfunction we are talking about.

Common error codes for air conditioners of various brands

Self-diagnosis systems of modern equipment, with the help of which air conditioning is carried out, are designed to self-check the performance of split systems, and if a malfunction is detected, notify users by displaying error codes on the displays of internal modules and/or remote controls.

Modern air conditioners and split systems are created on the basis of microprocessors, which leads to almost complete automation of the air conditioning control process, and, in addition, allows monitoring the serviceability of the equipment and how it works. Moreover, the microprocessor stops the system if it detects a malfunction, and, in addition, provides real assistance to specialists in identifying faulty components and parts by displaying error codes on the screen.
Next, we will discuss in more detail the most common error codes for air conditioning systems of popular brands.

Panasonic air conditioner error codes

Panasonic air conditioners enjoy well-deserved popularity due to their modern design, high build quality, reliability, and almost silent operation. However, they are also susceptible to breakdowns from time to time, which their owners are notified of by displaying codes on the displays indicating a particular malfunction.

Codes Decoding the code and the essence of the problem Causes of the problem
Error H11 The air conditioner error code indicates a communication failure between the external and internal units, which is not established after thirty seconds from the moment the unit starts. After the indicated error is recorded, it is likely that the fan of the indoor unit will work. The occurrence of the indicated malfunction may be due to incorrect installation of interconnect wires. In addition, in this way the processor can signal the failure of the electronic control boards of the external and internal units.

Error H14

With this code, the processor notifies users that the internal (room) air temperature sensor is faulty. This error records the fact that the temperature in the room is too high or, conversely, too low. This malfunction is due to an open circuit or short circuit (short circuit) in the sensor.

Error H19
Thanks to this error, the user learns that the indoor unit motor (IMU) is jammed. This is manifested by a discrepancy between the actual speed and the value set by the processor. This malfunction can occur for several reasons:

· breakdowns of the motor itself;

· failure of the indoor unit board;

· malfunction of the MVB wire connectors.


Error H21
The display of this code on the air conditioner display indicates a malfunction of the float sensor

drain pan of the indoor unit.

This malfunction is caused by a clogged drainage system. In such a situation, you should check the sensor logic and the resistance of the pump motor windings.

Error H23
The indicated error indicates a violation of the operating mode of the basic sensor (No. 1) of the temperature of the heat exchanger of the indoor unit.

The problem can be caused by a broken sensor, or a short circuit in the specified sensor.


Error H24
Thanks to this error, users will learn that sensor No. 2 of the heat exchanger temperature in the indoor unit has failed. The reasons for the problem are the same as in the case of sensor No. 1.
Error H27 This code is evidence that the outside air temperature sensor is broken.

The problem is due to the same reasons as stated in the previous two paragraphs.

Error H28

The indicated error indicates a malfunction of sensor No. 1 of the temperature of the outdoor unit. The failure may also be due to an open circuit or a short circuit in the sensor.
Error H30 We are talking about a failure of the compressor discharge temperature sensor. The problem may be due to an open circuit or short circuit.

Error H35

This is an error in the operation of the drain pump. This breakdown is usually caused by a clogged drainage system. To restore the operation of the drain pump, the resistance of the windings is usually checked

its motor, the value of which should be approximately 200 Ohms.

Error F11

This code is displayed when the four-way switching valve is not operating correctly.
cold/warm.
The indicated problem may be due to a malfunction of the solenoid coil of the valve in question.

In addition to those already listed above, there are error codes for Panasonic air conditioners, for example, those that indicate problems:

  • with temperature sensors in the internal units of air conditioners;
  • with air temperature sensors;
  • with evaporator temperature sensors;
  • with temperature and pressure sensors;
  • with radiator temperature sensors;
  • with protective devices, etc.

And these are not all error codes for Panasonic air conditioners, and they are not needed by ordinary users, since the repair of the units under discussion should be trusted only to professionals, for example, those who work at the Moscow service center “ETekhnik”.

LG air conditioner error codes

Another very popular brand of household appliances is LG air conditioners and split systems, which is due to its significant advantages: original design, a wide variety of colors, excellent quality, a large number of different, including innovative functions, and, of course, a high degree of reliability. But breakdowns also occur with these units, and therefore their lucky owners will need information about error codes for LG air conditioners.

Error code LED blinking order for faults Causes
problem arises

Trouble-shooting

Error 1 One flash every 3 seconds This code indicates that one of the thermistors on the indoor unit board, which controls the temperature of the outside air and the refrigeration circuit tube of the unit, is faulty. This may be caused by an open circuit or a short circuit. To eliminate the malfunction, first check the thermistors, and if necessary, replace the internal unit of the split system.

Error 2

Two blinks every 3 seconds This error indicates a failure of one of the thermistors of the outdoor unit. We are talking about the outside air temperature sensor or the refrigeration circuit pipe of the unit. If such an error is displayed, the wizard first checks for
malfunctions in thermistors.

Error 3
3 flashes every 3 seconds This error indicates that the split system is operating simultaneously for both heating and cooling. If we talk about the causes of the malfunction, then in such cases, as a rule, there is an error when connecting the split system during its installation.

Error 4
4 flashes every 3 seconds This error indicates that the compressor overload protection is activated.

If the error under discussion occurs, the specialist checks the compressor overload protection system for current overload, gas pressure in the system, etc.


Error 5
5 flashes every 3 seconds

This error indicates a violation in the exchange of data between the indoor and outdoor units of air conditioners with each other.

We are most likely talking about a violation of the connection between the outdoor and indoor units. In this case, the cable lines are checked for possible breaks or short circuits. To eliminate a malfunction, it is often necessary to change the interconnect cable.

Error 6
6 flashes every 3 seconds This error indicates the existence of a problem related to the fact that one or more relays of the outdoor unit consumed a current higher than normal for a short period of time. To eliminate the problem, the serviceability of the actuators of the outdoor unit is checked, and, in addition, there is a possibility that their controls are faulty - we are talking about the key power relays.
Error 7
7 flashes every 3 seconds

This error indicates that the outdoor unit has consumed higher than normal current for a long time.

When such an error occurs, the technician checks the refrigerant pressure in the vaporizer-condenser system, and, in addition, checks the elements of the external module for serviceability

air conditioners.

Error 8

8 flashes every 3 seconds The indicated error indicates that the fan motor is faulty, which, naturally, is manifested by a violation or lack of rotation of the fan. If this error occurs, the engine, elements of its control circuit and terminal contacts are checked for serviceability.
Error 9
9 flashes every 3 seconds
This error indicates a malfunction of a part such as a four-way valve. When the indicated error occurs, the specified valve is checked to ensure its serviceability.

Error 10

10 flashes every 3 seconds This error is an indication of a malfunction of the thermistor, which monitors the temperature of the compressor housing. The problem may be due to a network break or short circuit. After checking the serviceability of the thermistor, it is changed, if necessary.

Error codes for Mitsubishi Heavy air conditioners

Mitsubishi Heavy Ind is one of the world leaders in the production of, in particular, household air conditioners and split systems. This is not surprising, since climate control equipment of this brand is characterized by a number of undoubted advantages, for example, we are talking about:

  • about durability;
  • about efficiency;
  • the presence of a large number of functions;
  • about low noise level;
  • about high power;
  • about the comfort of air conditioning;
  • about reliability, etc.

However, as you know, “nothing lasts forever,” and therefore reliable air conditioners of this brand are prone to breakdowns. It is very convenient that these “smart” devices are capable of self-diagnosis and notify their owners that a particular malfunction has been detected. The conversation is about error codes for Mitsubishi air conditioners, the most common of which can be found in the table below.

Air conditioner error codes
Mitsubishi Heavy

How to decipher error codes for Mitsubishi Heavy air conditioners
E1 This error indicates that the printed circuit board of the indoor unit is faulty, or it is a malfunction or incorrect connection of the remote control.

E3
The indicated error indicates that the address of the outdoor unit is incorrect.

E5
The indicated error is evidence of a malfunction of the control board of the outdoor module.

E6
This error indicates a malfunction of the evaporator temperature sensor, which can be caused by its break or short circuit.
E8 This error indicates that the evaporator is overcurrent or that the sensor is faulty.
This error indicates that the addresses are configured incorrectly.
This code indicates that a fan error has occurred.
E28 This error is evidence of a malfunction of the control panel sensor.
The indicated code is evidence that there was an error in connecting the outdoor and indoor units.
E33 This is an error indicating a break in the compressor winding.
E35 The indicated error indicates a high temperature of the condenser or

temperature sensor malfunction.

E37 The occurrence of this code is due to a malfunction of the condenser temperature sensor.
E38 This error occurs if there is a malfunction in the outside air temperature sensor.
E39 This code indicates that there is an error in the discharge pipe temperature sensor.

E49

The indicated error indicates that there is a malfunction associated with a system shutdown, which occurred due to insufficient refrigerant or low pressure, which, in turn, can be caused, in particular, by a refrigerant leak.

This error indicates a disconnect

low pressure sensor.

E63 This error indicates a malfunction associated with an emergency shutdown of the indoor unit.

The ability of modern air conditioning systems to self-diagnosis and issue error codes is extremely helpful in identifying their malfunctions, which significantly speeds up and facilitates the repair of this equipment. However, it should be noted that there are a huge number of error codes for air conditioners of any brand, but they are usually used by specialists. For example, with regard to Mitsubishi Heavy air conditioners, in addition to those already mentioned, there are error codes indicating that there are problems:

  • with internal non-volatile memory;
  • with indoor block temperature sensor;
  • with blocking sensor;
  • with high pressure sensor;
  • with current sensor;
  • with motor or fan board;
  • with indoor module fan motor;
  • with fan motor;
  • with compressor motor, etc..

Let us note that if one or another malfunction of air conditioners is detected, they should be repaired by resorting to the services of professionals, in particular those who work at the Moscow service center “ETekhnik”.

Toshiba air conditioner error codes

Toshiba air conditioners are very worthy representatives of modern climate control equipment, which compare favorably with similar equipment from other brands in their compactness and unique style. Therefore, error codes for Toshiba air conditioners are of interest not only to specialists who repair household appliances, but also to the owners of these units.

Air conditioner error codes
Toshiba

How Toshiba air conditioner error codes are deciphered
00-0d

This code indicates that there is an error in the control board or the sensor responsible for the temperature of the radiator is faulty.


01-04
This error indicates that the board or its fuses have burned out. In addition, this code may indicate that there is an interblock connection error.

01-05
This error indicates a malfunction of the inverter board.

02-17
The indicated error indicates a malfunction in the compressor current sensor.
02-19 This code indicates that a board temperature sensor error has occurred.

This table shows only a small part of the errors detected by self-diagnosis. In fact, error codes for Toshiba air conditioners, as well as other brands, are presented much more widely. The codes cover many faults, for example those related to:

  • with protection problems in external units;
  • with problems with the power of indoor units;
  • with malfunctions of external heat exchangers;
  • with cooling problems;
  • with communication errors;
  • with connection errors of outdoor units;
  • with errors on internal units;
  • with breakdowns of external unit circuit boards;
  • with poor engine performance;
  • problems with controller signal transmission;
  • with problems associated with the fact that an error occurred in some sensor;
  • with malfunctions of power modules;
  • with fan motor overload;
  • with problems related to the supply voltage;
  • with high outlet air temperature;
  • with a malfunction of the air temperature sensor in the system;
  • with problems with sensors, etc.

All the indicated and many other malfunctions, which are indicated by air conditioner error codes, will be quickly and efficiently eliminated by experienced craftsmen of the Moscow service center "ETekhnik" at more than reasonable prices. By the way, the specialists of this company will eliminate any malfunction of household appliances of all well-known brands.

Daikin air conditioner error codes

The demand for high-quality, reliable Daikin air conditioners is well known. But since they, like any other household and other appliances, sometimes fail, their error codes are certainly of interest to users. This is not surprising, because error codes, in fact, are very useful “readings” that reflect the results of self-diagnosis of air conditioners, which is of great benefit, first of all, to specialists in finding any malfunction.

The table below shows the most common error codes for Daikin air conditioners.

Daikin codes
How to decipher Daikin codes

Code A0

This error indicates that the general protective device has tripped.

Code A9
If the indicated error appears on the display of the air conditioner of the brand under discussion, this indicates a malfunction of the electronic expansion valve.

Code A7
This error indicates that the air conditioner has a faulty shutter drive.

Code EF
This error indicates that the heat storage unit is faulty.
Code JA This error is evidence of a faulty compressor discharge sensor.

FA code

The indicated error on the air conditioner display indicates a malfunction that results in an unacceptable level of discharge pressure.

Code FF
This error indicates the presence of a malfunction, which results in an unacceptable oil level.

Code 6H

This error alerts the owner of the air conditioner that the door switch is open.
Code E2 This code indicates that there is a malfunction that occurred during the zero crossing.
Code P5 The appearance of the indicated code on the air conditioner display indicates a malfunction that occurred due to high or low temperature.
Code CU-2E This code indicates a malfunction of the temperature sensor in the compressor discharge tube.
Code E6 The occurrence of this code is an indicator of a malfunction caused by the blocking of the air conditioning system compressor motor due to excess current.

Code H6

The appearance of this code indicates a malfunction associated with the lack of a feedback signal from the fan motor.

Aeronik error codes

Aeronik air conditioner error codes

E1 – compressor discharge pressure has increased;
E2 – freezing of the heat exchanger of the indoor unit has occurred;
E3 – compressor discharge pressure has decreased;
E4 – the temperature of the discharge pipeline has increased;
E5 – activation of the compressor current relay;
F0 – there is a malfunction in the internal air temperature sensor
room, in the heat exchanger in the indoor unit or ambient air in the outdoor unit;
F0 -- There may also be a freon leak in the indoor unit.
E6 – there are faults in switching;
E8 – the motor of the indoor unit is overloaded;
F1 – there is a malfunction in the temperature sensor in the heat exchanger;
F4 – a malfunction has occurred in the temperature sensor of the discharge
air room.
H1- is not an error. The air conditioner has switched to auto defrost mode.

Airwell Error Codes

Error codes for Airwell air conditioners



Akvilon error codes

Error codes for Akvilon air conditioners

Possible mistakes

Monitor mode 1

(indicator on

display)

Monitor mode 2

(wire controller)

Order of appearance

Actions

Communication error

Shutdown

Drainage system error

The indicator lights up 4 times/8sec

Shutdown

Phase failure, phase loss or low voltage error

The indicator lights up 6 times/8sec

Shutdown

The indicator lights up 1 time/8sec

Shutdown

Indoor unit sensor(TE) abnormality

The indicator lights up 2 times/8sec

Shutdown

The indicator lights up 2 times/1sec

Continue working

Internal overheat protection

Shutdown

Defrosting (not error)

The operation indicator lights up

Continue working

Fault codes for power supply 380-415W

Suitable for 36000~60000BTU units, with 380-415W 3N, 50Hz power supply

Possible mistakes

Display mode1

(panel indicator

display)

Display mode 2

(indicator

errors on the control panel)

Display mode3

(controller

wires)

Order of appearance

Actions

Communication error

Lights up 5 times and goes out after 2 seconds

Shutdown

Communication error with wire controller

Shutdown

Drainage system error

Lights up 4 times and goes out after 2 seconds

Shutdown

External protection (Phase loss)

Lights up 6 times and goes out after 2 seconds

Shutdown

External protection (overheating discharge)

Lights up 10 times and goes out after 2 seconds

Shutdown

High pressure protection

Shutdown

Low pressure protection

Lights up 9 times and goes out after 2 seconds

Shutdown

Room temperature sensor abnormality (Air temperature)

Lights up once and goes out after 2 seconds

Shutdown

Indoor unit (TE) sensor abnormality

Lights up 3 times and goes out after 2 seconds

Shutdown

Outdoor unit sensor abnormality (TW)

Lights up 2 times and goes out after 2 seconds

Lights up 2 times and goes out after 2 seconds

Continue working

External condensate temperature sensor(TL) anomaly

Lights up 7 times and goes out after 2 seconds

Continue working

Temperature sensor(TP) discharge anomaly

Lights up 8 times and goes out after 2 seconds

Continue working

Ballu error codes

Error codes for Ballu air conditioners


E1 – short circuit or break of the sensor responsible for the indoor unit.
E2 - short circuit or break in the sensor responsible for the temperature of the capacitor.
E3 - short circuit or break in the sensor responsible for the evaporator temperature.
E4 - short circuit or break in the sensor responsible for the indoor unit.
E6 – the protection of the external unit has tripped.
E8 – electrostatic filter is clogged.
P4 – an error occurred in the operation of the evaporator sensor due to high or
low temperature.
P5 – an error occurred in the operation of the capacitor sensor due to high or
low temperature.
P6 – defrosting mode has been activated or there has been a delay in operation
heat exchanger.

Carrier Error Codes

Carrier air conditioner error codes


2 – there is a malfunction of the temperature sensor in the room;
3 – there is a malfunction of the temperature sensor in the internal
heat exchanger;
6 – there are malfunctions in the operation of the reversing valve in the outdoor unit;
8 – a malfunction has occurred in the fan motor located in
indoor unit;
9 – no electrical power to the indoor unit;
11 – there are malfunctions in the drainage pump;
12 – a software failure occurred in the indoor unit;
13 – an error occurred in the configuration;
14 – signal lost in the central control system;
15 – there is a malfunction of the temperature sensor in the internal
heat exchanger;
18 – there are malfunctions in the control of the outdoor unit;
20 – block position is not recognized;
21 – there is a malfunction of the current sensor located in the outdoor unit;
22 – there is a malfunction of the temperature sensor in the external
heat exchanger;
23 – a malfunction of the discharge temperature sensor has occurred;
24 – there are malfunctions in the operation of the fan in the outdoor unit;
26 – other malfunctions in the outdoor unit;
27 – the compressor located in the outdoor unit is blocked;
28 – the discharge temperature is unacceptable;
29 – a malfunction has occurred in the compressor, located in the outdoor unit;
31 – there was an increase in pressure in the circuit of the outdoor unit.

Cooper&Hunter error codes

Error codes for Cooper&Hunter air conditioners (Cooper&Hunter)

Code E0 - exceeding the lower starting voltage threshold. Starting the frequency controller.
Code E1 - excess pressure. Starting the compressor protection system.
Code E2 - threat of freezing of the indoor unit. Starting the protection system.
Code E3 - lowering the permissible pressure threshold. Starting the compressor protection system.
Code E4 - exceeding the permissible temperature of the discharge tube. Starting the protection system.
Code E5 - compressor overload. Starting the protection system.
Code E6 - error in connection/operation of the signal or power cable.
Code E7 - the installed split system modes do not match.
Code E8 - evaporator overheating. Starting the protection system.
Code E9 - startup of the cold air supply protection system in thermal mode.
Code F0 - failure of the temperature rise sensor.
Code F1 - failure of the evaporator temperature sensor.
Code F2 - failure of the condenser temperature sensor.
Code F3 - failure of the air temperature sensor in the system.
Code F4 - failure of the blower temperature sensor.
Code F5 - failure of the compressor discharge tube sensor.
Code F6 - condenser overheating.
Code F7 - there is insufficient lubrication in the compressor crankcase.
Code F8 - compressor overloaded. Starting the protection system.
Code F9 - exceeding the maximum condenser temperature due to a decrease in fan speed during cooling. The compressor is overloaded.
Code FF - there is no power supply to one of the phases / error in the operation of the phase monitor.
Code FA - condenser/evaporator overheating. Starting the protection system.
Code FH - danger of evaporator freezing. Starting the protection system.
Code H0 - overheat protection activated.
Code H1 - condenser defrost mode is activated.
Code H2 - error in the operation of the electrostatic filter. Starting the protection system.
Code H3 - exceeding the permissible compressor temperature. Starting the protection system.
Code H4 - error in the system.
Code H5 - start of the IPM inverter unit protection system.
Code H6 - sensor malfunction. Lost return signal from fan motor.
Code H7 - compressor is faulty.
Code H8 - drainage system is full. Start protection.
Code H9 - malfunction of the electric heater of the indoor unit.

Daikin error codes

Error codes for Daikin air conditioners


A0 – activation of the protective device.
A1 – problems with the printed circuit board.
A2 – fan motor is blocked.
A3 – abnormal level of drainage.
A4 – problems with the heat exchanger.
A5 – abnormal temperature in the heat exchanger.
A6 – fan motor overloaded.
A7 – the blind drive is faulty.
A8 – current overload of the device.
A9 – expansion valve is faulty.
AA – engine overheated.
AH – air filter contamination.
AC – idle speed detected.
AJ – insufficient performance.
AE – poor water supply.
AF – humidifier defect detected.
C0 – sensor is faulty.
C3 – the sensor responsible for the drainage system is faulty.
C4 – the sensor responsible for the temperature of heat exchanger 1 is faulty.
C5 – the sensor responsible for the temperature of heat exchanger 2 is faulty.
C6 – fan motor is overloaded.
C7 – the sensor responsible for driving the blinds is faulty.
C8 – the sensor responsible for the input current is faulty.
C9 – the air inlet thermistor is faulty.
CA – outlet air thermistor is faulty.
CH – high level of pollution.
CC – humidity sensor is faulty.
CJ – the temperature sensor located on the control panel is faulty.
CE – radiation sensor is faulty.
CF – the sensor responsible for high pressure is faulty.

Error codes for the outdoor unit of Daikin air conditioners (Daikin)

E0 – the protective device has tripped.
E1 – the printed circuit board located in the outdoor unit is faulty.
E3 – activation of the sensor responsible for high pressure.
E4 – activation of the sensor responsible for low pressure.
E5 – overheating relay or compressor motor overloaded.
E6 – compressor motor is blocked.
E7 – fan motor is blocked.
E8 – current overload detected.
E9 – expansion valve is faulty.
AH – the pump is blocked.
EJ – activation of an additional protective device.
EE – the permissible water level in the drainage system has been exceeded.
EF – the unit responsible for storing heat is faulty.
H0 – general sensor malfunction.
H1 – the sensor responsible for the air temperature is faulty.
H2 – the sensor responsible for electrical power is faulty.
H3 – the sensor responsible for high pressure is faulty.
H4 – the sensor responsible for low pressure is faulty.
H5 – the overload sensor is triggered or the compressor is not functioning.
H6 – the blocking sensor is triggered or the compressor is overloaded.
H7 – the blocking sensor is triggered or the fan is overloaded.
H8 – activation of the sensor responsible for the input voltage.
H9 – activation of the sensor responsible for the outside air temperature.
HA – activation of the sensor responsible for the output air.
HH – activation of the sensor responsible for blocking the water pump.
HC – activation of the sensor responsible for hot water.
HE – activation of the sensor responsible for the drainage system.
HF – an accident occurred in the heat storage unit.
F0 – activation of devices No. 1 and No. 2, responsible for protection.
F1 – activation of device No. 1, responsible for protection.
F2 – activation of device No. 2, responsible for protection.
F3 – temperature in the discharge pipe is too high.

Dantex Error Codes

Error codes for Dantex air conditioners (Dantex)


E1 – an error occurred in the non-volatile memory;
E2 – a zero crossing error has occurred;
E3 – no control of the fan speed of the indoor unit;
E4 – overvoltage protection mode is in effect;
E5 – there is no contact with the open temperature sensor control;
E6 – there is no contact with the evaporator temperature sensor control.

Chillers Dantex (DN)

E0 – an error has occurred in the operation of the water flow meter;
E1 – an error occurred when connecting the phases;
E2 – a communication error has occurred;
E3 – an error has occurred in the outlet water temperature sensor;
E4 - an error has occurred in the water temperature sensor at the outlet
shell and tube heat exchanger;
E5 – error in the operation of capacitor A;
E6 – error in the operation of capacitor B;

E8 – an error has occurred in the charge air temperature sensor;
E9 – an error has occurred in the flow meter;
EA – the main block revealed a decrease in the number of additional blocks;
EB – malfunctions of the frost protection system;
EC – malfunction of the drive controller;
ED – an error has occurred in the control system and communication between blocks;
Ed – electrical protection tripping;
EE – an error has occurred in the connection between the microprocessor and the control panel;
EF – an error has occurred in the inlet water temperature sensor;
RO - overheating or increased pressure has occurred;

P2 – the pressure has increased or the air in system B has overheated;
P3 – pressure in the system has decreased;
P4 – there was an overcurrent in system A;
P5 – there was an overcurrent in system B;
P6 – the pressure in the condenser of system A has increased;
P7 – the pressure in the condenser of system B has increased;
P8 – malfunction of the compressor discharge temperature sensor in system A;
Рb – protection against freezing;
PE – the temperature in the heat exchanger has decreased;
F1 – errors in the operation of permanent memory;
F2 – errors in the operation of wired controllers.

Elektrolux error codes

Error codes for Elektrolux air conditioners


E1 – pressure level exceeded;
E2 – the indoor unit has frozen;
E3 – pressure level too low;
E4 – compressor malfunction;
E5 – current overload has occurred;
E6 – there is no connection between the indoor and outdoor units;
E7 – a conflict has occurred in the operating modes of the indoor units;
E8 – the indoor unit fan is overloaded;
E9 – drainage bath is overfilled;
F0 – malfunction of the temperature sensor in the indoor unit;
F1 – malfunction of the temperature sensor entering the heat exchanger
in the indoor unit;
F2 – malfunction of the temperature sensor in the middle part

F3 – malfunction of the temperature sensor at the outlet
heat exchanger in the indoor unit;
F4 – malfunction of the ambient air temperature sensor;
F5 – malfunction of the outdoor unit temperature sensor;
F6 – malfunction of the temperature sensor entering the heat exchanger
in the outdoor unit;
F7 – malfunction of the temperature sensor of the outlet
heat exchanger in the indoor unit;
F8 – malfunction of the first discharge temperature sensor
compressor;
F9 – malfunction of the second discharge temperature sensor
compressor;
FA – malfunction of the crankcase temperature sensor of the 1st compressor;
FB – malfunction of the crankcase temperature sensor of the 2nd compressor;
FC – malfunction of the high pressure sensor;
FD – malfunction of the low pressure sensor;
EH – malfunctions in the operation of the additional heater.

Fuji Error Codes

Error codes for Fuji air conditioners


E00 – an error occurred in the connection between the remote control and the indoor unit;
E01 – an error occurred in the communication between the indoor and outdoor modules;
E02 – malfunction of the room temperature sensor;
E03 – a short circuit has occurred on the room temperature sensor;
E04 - an error occurred in the operation of the temperature sensor on the internal
heat exchanger;
E05 - a short circuit has occurred on the internal temperature sensor
heat exchanger;
E06 - an error occurred in the operation of the temperature sensor on the outside
heat exchanger;
E07 - a short circuit has occurred on the outside temperature sensor
heat exchanger;
E08 – the supply of electrical energy is interrupted;
E09 - the container intended for collecting condensate has overflowed;
E0R – malfunction of the outdoor unit temperature sensor;
E0B – a short circuit has occurred on the temperature sensor of the outdoor unit;
E0C - requires opening the temperature sensor on the drain pipe;
E0D – a short circuit has occurred on the temperature sensor of the drain pipe;
E0F – the outlet temperature is too high or too low;
E11 – malfunction of the control board;
E12 – malfunction of the indoor unit fan;
E13 – the system sends incorrect signals;
E14 – error in non-volatile memory.

General Climate Error Codes

Error codes for General Climate air conditioners


E2 – short circuit or break in the sensor responsible for the internal temperature
air.
E3 – short circuit or break in the sensor responsible for the evaporator temperature.
E4 – short circuit or break in the sensor responsible for the temperature of the condenser.
E5 – an error occurred in the operation of the drainage pump.
E6 – error in the protection of the external unit.
E7 – EEPROM error occurred.
E8 – the drain pan overflow protection has activated.

Gree Error Codes

Gree air conditioner error codes


E1 – compressor protection against too high pressure has tripped.
E2 – the frost protection of the indoor unit has activated.
E3 – compressor protection against too low pressure has tripped.
E4 – high temperature protection of the discharge tube has been activated.
E5 – system or compressor overload protection has tripped.
E6 – problems have been detected in the signal or power cables.
E7 – contradictions in the established regime.
E8 – protection of the electric motor or evaporator from overheating has tripped.
E9 – protection against the entry of cold air during heating has tripped.
E0 – frequency regulator protection against too low starting voltage has been triggered
voltage.
H6 – no return signal from the fan motor.
F0 – discharge temperature sensor is faulty.
F1 – the sensor responsible for the evaporator temperature is faulty.
F2 – the sensor responsible for the temperature of the condenser is faulty.
F3 – the sensor responsible for the air temperature in the system is faulty.
F4 – the sensor responsible for the supercharger temperature is faulty.
F5 – the sensor responsible for the compressor discharge tube is faulty.
F6 – capacitor overheating detected.
F7 – oil loss from the compressor is detected.
F8 – system or compressor overload protection has tripped.
F9 – compressor protection against high temperatures has tripped.
FF – there is no power in one of the phases or the phase monitor is faulty.
H1 – defrosting occurs.
H2 – electrostatic filter protection has tripped.
H3 – protection against severe overheating has tripped.
H4 – a system failure has occurred.
H5 – IPM block protection is triggered.
H7 – problems with the compressor.
H8 – activation of the drainage system overflow protection.
H9 – electric heater malfunction.
H0 – overheating protection triggered.
FA – activation of condenser or evaporator protection against overheating.
FH – activation of the evaporator antifreeze protection.

Error codes Green

Error codes for Green air conditioners


U1 - Current phase fault, circuit detection for compressor. Flashes 13 times. During cooling and drying operation, the compressor will stop while the indoor fan will run. When operating in heating mode, the complete unit will stop. Replacement of external control panel AP1.

U3 - Malfunction of the voltage falling on the DC buses. Flashes 20 times. During cooling and drying operation, the compressor will stop while the indoor fan will run; When operating in heating mode, the complete unit will stop.
The supply voltage is unstable.

U5 - Full unit current fault detection. Flashes 13 times. During cooling and drying operation, stop the compressor while the indoor fan is running; During heating operation, the complete unit will stop the operation. There is a fault in the circuit on the outdoor units control panel AP1, please replace the outdoor unit control panel AP1.

U7 - Blinks 20 times. If this fault occurs during heating operation, the device will stop working. 1. Supply voltage is lower than AC175V; 2.Wiring terminal 4V loose or broken; 3. 4V will be damaged, please replace the cable.

U8 - Zero transition inspection circuit malfun-fiction Fan PIN moto. Flashes 17 times every 3s Remote controller operation or
The control panel is available, but the units will not operate. The discharge rate of the capacitor is slow, which causes the controller to make incorrect decisions. Zero crossing detection circuit of the main board abnorma. Contact flowchar repair.

U9 - Zero crossing malfunction of the outdoor unit. Flashes 18 times. During cooling operation, the compressor will stop while the indoor fan will run; During heating, the device will not work. Replacement of external control panel AP1.

Haier Error Codes

Error codes for Haier air conditioners

E0 Malfunction of condensate drainage function.
E1 The compressor has increased pressure.
E2 The heat exchanger of the indoor module is covered with ice.
E3 Insufficient pressure in the compressor.
E4 Compressor overheating.
E5 The compressor is switched off due to increased load.
E6 No communication between blocks.
E7 The indoor module does not respond to commands from the remote control.
E8 Overload of the electric motor of the indoor module.
F0 The temperature sensor in the room has turned off.
F1 The temperature sensor of the indoor module heat exchanger has turned off.
F2 The temperature sensor of the heat exchanger of the external module has turned off.
F3 The outdoor temperature sensor has turned off.
F4 The temperature sensor on the air supply has switched off.
FF The power supply is interrupted.

Hisense Error Codes

Error codes for Hisense air conditioners

Possible causes of the malfunction:
1 Error in outdoor unit heat exchanger temperature sensor a. The outdoor unit heat exchanger temperature sensor circuit is open; b. The temperature sensor of the outdoor unit heat exchanger is faulty; With. The outdoor unit control circuit board is faulty
2 Compressor discharge temperature sensor error a. The temperature sensor circuit in the compressor discharge line is open; b. The temperature sensor in the compressor discharge line is faulty; With. The outdoor unit control circuit board is faulty
5 Integrated Power Module (IPM) protection trip a. The Integrated Power Module (IPM) circuit board is faulty; b. The fan of the outdoor unit has failed; c. The electric motor of the outdoor unit fan is faulty; d. The outdoor unit fan is blocked; e. The condenser is dirty; f. The rules for installing the outdoor unit have not been followed.
6 Operation of the AC overvoltage or undervoltage protection device a. The network voltage is above or below the maximum permissible values; b. The unit supply voltage is above or below the maximum permissible values
7 Communication error between indoor and outdoor units a. Broken connecting cable; b. The connecting cable is damaged; With. Incorrect connection or broken connection between the filter board and the outdoor unit control circuit board
8 Overload protection device a. Fan motor malfunction; b. The evaporator and condenser are dirty; c. The air intake and air outlet are blocked; d. The printed control of the outdoor unit is faulty; e. Compressor faulty
10 Communication error between two microcircuits (control and drive) in the printed circuit. Poor cable connection b. The printed circuit board of the outdoor unit or the circuit board of the drive is faulty;
11 Outdoor unit EEPROM memory error a. Poor quality soldering of the EEPROM chip; b. EEPROM chip installation error (incorrect position); .EEPROM chip malfunction
12 Triggering of the protection device at low outside temperatures a. This protection is triggered if the outside air temperature drops below 15°C; b. The outside air temperature sensor is faulty; With. The control circuit board of the outdoor unit is faulty.
13 Activation of the protection device as a result of increased temperature in a. The temperature sensor in the compressor discharge line is faulty; b. Insufficient refrigerant charge in the system
14 Outside air temperature sensor error a. The outside air temperature sensor circuit is open; b. The outside air temperature sensor is faulty; With. The outdoor unit control circuit board is faulty
15 Activation of compressor thermal protection due to overheating a. Compressor discharge temperature sensor open circuit b. Insufficient refrigerant charge in the system
16 Triggering of the heat exchanger protection device against freezing or overload when the indoor unit is operating in heating mode a. Normal operation of the protection device when the heat exchanger freezes or overloads; b. The indoor unit heat exchanger temperature sensor circuit is open; c. The temperature sensor of the indoor unit heat exchanger is faulty; d. The indoor unit control circuit board is faulty; e. Refrigerant circulation problem
17 Power factor compensation (PFC) a. The reactive power compensation device is faulty; b. The circuit board of the outdoor unit drive is faulty
18 DC compressor start error a. Incorrect connection or breakage of the compressor power cable; b. The circuit board of the integrated power module (IPM) of the outdoor unit is faulty; c. Outdoor unit control circuit board is faulty d. Compressor faulty
19 Compressor drive error a. Incorrect connection or breakage of the compressor power cable; b. The circuit board of the integrated power module (IPM) of the outdoor unit is faulty; c. Outdoor unit control circuit board is faulty d. Compressor faulty 7. Troubleshooting
20 Triggering of the device protecting the electric motor of the outdoor unit fan from operation with a locked rotor a. The circuit of the outdoor unit fan motor is open; b. The outdoor unit fan is blocked; With. The fan motor is faulty; d. The outdoor unit control circuit board is faulty

Hitachi Error Codes

Error codes for Hitachi brand air conditioners


01 – reversing valve malfunction or not normal
media temperature.
02 – the mode that forcibly starts the external module is activated.
03 – there is no connection between the external and internal modules.
04 – equipment malfunction, you should pay attention to the readings
other indicators.
06 – irregularities were detected in the operation of the pump that pumps out condensate.
07 – manual start of the pump is required.
08 – engine functions are impaired.
09 – there is no connection with the PCB thermistor.
10 – incorrect fan operation.
13 – PCB is not functioning.

Hyundai Error Codes

Hyundai air conditioner error codes

0 – error in non-volatile memory;
E1 – an error occurred in connecting the blocks: indoor and outdoor;
E2 – malfunction of the outdoor unit sensor;
E3 – malfunction of the indoor unit fan motor;
E4 – there is a break (short circuit) in the internal air temperature sensor;
E5 – there is a break (short circuit) in the evaporator temperature sensor;
EC - coolant leak has occurred.

Jax Error Codes

Error codes for Jax air conditioners


E2 – a malfunction has occurred in the indoor air temperature sensor;
E3 – there is a malfunction in the evaporator temperature sensor;
E4 – there is a malfunction in the condenser temperature sensor;
E5 – an error occurred in the operation of the drainage pump;
E6 – protection in the external unit has tripped;
E7 – failures in non-volatile memory;
E8 – drain pan is full.

Kentatsu Error Codes

Error codes for Kentatsu air conditioners


E1 – there is no contact with the air temperature sensor in the internal
block;
E2 – there is no contact with the evaporator temperature sensor;

E4 – there is no contact with the outdoor air temperature sensor;
E5 – there is no contact between the indoor and outdoor units;
E6 – warning about overheating or freezing of the outdoor module;
E10 – there was a pressure failure in the compressor;
E13 – electricity is not supplied due to the wires being mixed up;
E14 – supply of electricity to the wrong phase;
P4 – the evaporator has overheated;
P5 – the capacitor has overheated;
P7 – excess temperature level in the compressor;
P9 – antifreeze protection is turned on;
P10 – the air outlet value is incorrect;
P11 – pressure during air intake exceeds permissible limits;
P12 – supply of high voltage current;
HS – the outdoor module is defrosting.
EC - Freon leak.

Models Kentatsu KSGH/KSRH

E1 – errors occurred in non-volatile memory;
E2 – a failure occurred during the transformation of the zero cycle;
E3 – incorrect fan rotation;
E4 – supply of too high voltage to the compressor;
E5 – there was a communication failure with the internal air temperature sensor;
E6 – there was a communication failure with the evaporator temperature sensor.

Models Kentatsu KSFU/KSRU

P4 – the evaporator of the indoor module has overheated;
P5 - the condenser of the outdoor module has overheated;
P9 – thawing is in progress;
E1 – no voltage to temperature sensors;
E2 – there is no connection with the evaporator temperature sensor;
E3 – there is no contact with the condenser temperature sensor;
E6 – a malfunction has occurred in the external module.

Duct type air conditioners

E0 – malfunction of the temperature sensor in the room;
E1 – a malfunction has occurred in the operation of the evaporator temperature sensor;
E2 – a malfunction has occurred in the temperature sensor of the external module;
E3 – there is no connection with the outdoor module;
E4 – a malfunction has occurred in the condenser pump;
E5 – errors in non-volatile memory;
E6 – the condensate tray is full.

Lessar error codes

Lessar air conditioner error codes


E0 – an error has occurred in the flow sensor;
E1 – incorrect phase rotation;
E2 – a communication error has occurred;
E3 – an error has occurred in the direct water temperature sensor;
E4 – an error has occurred in the temperature sensor of the shell-and-tube heat exchanger;
E5 – an error has occurred in the temperature sensor of condenser pipe A;
E6 – an error has occurred in the temperature sensor of condenser pipe B;
E7 – an error has occurred in the outside air temperature sensor;
E8 - an error has occurred in the compressor discharge temperature sensor
systems A;
E9 – an error has occurred in the flow temperature sensor;
EA – loss of communication with slave units has occurred;
P0 – pressure or temperature in system A is exceeded;
P1 – pressure in system A has decreased;
P2 – pressure or temperature in system B is exceeded;
P3 – pressure in system B has decreased;
P4 – there was an excess current in system A;
P5 – there was an excess current in system B;
P6 – the condensation temperature in system A is exceeded;
P7 – the condensation temperature in system B is exceeded;
P8 – temperature rise in the compressor;
Рb – protection against freezing.

LG Error Codes

Error codes for LG air conditioners (Elgie)


01 – a short circuit has occurred in the sensor responsible for air temperature,
or circuit break.
02 – there is a short circuit in the sensor responsible for temperature
evaporator, or open circuit.
03 – a poor connection has been detected between the drive console and
indoor unit.
04 - an error occurred in the operation of the drain pump or float
sensor responsible for the condensate level.
05 - an error was detected in the interconnection of internal and external
blocks.
06 – a short circuit has occurred in the temperature sensor responsible for the external
block or open circuit.
07 – internal multi-system units operate in different modes.
HL – the float sensor has opened.
CL - child lock activated.
Po – the device operates in jet cool mode.

MDV Error Codes

Error codes for MDV air conditioners


Free Match Series
Error indication on the indoor unit


Fault codes on the external unit

Universal external unit

Models with three-phase power supply with a capacity of 30, 36, 48, 60 Btu/h



Midea Error Codes

Error codes for Midea air conditioners


E0 – an error occurred in the non-volatile memory of the indoor unit.
E1 – an error occurred in the connection between the outdoor and indoor units.
E2 – an error occurred when crossing zero.
E3 – an error occurred during operation of the fan motor.
E4 – short circuit or break in the sensor responsible for the internal temperature
air.
E5 – short circuit or break in the sensor responsible for the evaporator temperature.
EC – refrigerant leak detected.

Mitsubishi Electric error codes

Error codes for Mitsubishi Electric air conditioners (Mitsubishi Electric)


P1 - an error has been detected in the input sensors.
P2 – error in the operation of the sensor responsible for the TH5 heat exchanger.
P4 – the drain pan is full or the CN4F sensor has broken.
P5 – an error occurred in the drain pump.
P6 – overheating or freezing has occurred.
P9 – error in the operation of the sensor responsible for the TH2 heat exchanger.
PA – the compressor is stopped forcibly.
E0, E3 – communication with the control panel is lost.
E1, E2 – problems with the control board.
E9, EE – there is no connection between the external and internal units.
U1. Ud – overheating protection has tripped, or sensor 63H has detected
high pressure.
U2 – low pressure detected in the supercharger, not enough refrigerant.
U3, U4 – short circuit or break in the temperature sensor of the external unit.
U5 - the condenser temperature does not correspond to the norm.
U6 – forced stop of the compressor or malfunction detected
power module.
U7 – lack of refrigerant or low pressure in the supercharger.
U8 – the fan motor installed on the external unit is stopped.
U9, UN – low or high supply voltage, or problems with
current sensor.
UF – the compressor is jammed or a current overload is detected.
UP – the compressor has stopped due to overload.
Fb – problems with the external unit control board.

Mitsubishi Heavy error codes

Error codes for Mitsubishi Heavy air conditioners (Mitsubishi Heavy)


E1 – a failure has occurred in the printed circuit board of the indoor unit or
malfunctions in the control panel;
E2 – duplication of addresses of internal units has occurred;
E3 – the address of the outdoor unit is incorrect;
E5 – a malfunction has occurred in the outer side control board;
E6 – there was a break (short circuit) of the evaporator sensor;
E7 – there is a break (short circuit) in the sensor of the indoor unit;
E8 – evaporator overload occurred;
E9 – error in the operation of the drainage pump;
E10 – more than 16 blocks are connected to the control panel;
E11 – more than 1 unit is connected to the control panel when the address is occupied;
E12 – errors in address settings;
E14 – incorrect settings of the master and slave connections have been made;
E16 – a malfunction has occurred in the operation of the indoor unit fan;
E28 - there is a malfunction in the control panel sensor;
E30 - an error occurred in connecting the outdoor and indoor units;
E31 – incorrect address settings;
E32 – there is a wire break or the phase sequence is incorrect;
E33 – wire winding has broken;
E34 – winding phase opens;
E35 - malfunction of the sensor or increase in temperature in
capacitor;
E36 – there was a deviation in the outlet air temperature above normal;
E37 – there is a malfunction in the condenser temperature sensor;
E38 – a malfunction has occurred in the outside air temperature sensor;
E39 – a malfunction has occurred in the temperature sensor of the discharge pipe;
E40 - there was an increase in pressure in the system;
E49 – a decrease in pressure has occurred or the refrigerant is insufficient;
E53 - there is a malfunction in the suction pipe thermistor;
E54 – low pressure sensor disconnected;
E55 - there is a malfunction in the temperature thermistor inside the compressor;
E56 - there is a malfunction or break in the power temperature sensor
transistor;
E57 – insufficient amount of coolant;
E59 – the compressor does not start;
E60 - an error occurred in the positioning of the compressor;
E63 - an emergency shutdown of the indoor unit occurred.

Neoclima error codes

Error codes for Neoclima air conditioners

Code E0 - error connecting indoor and outdoor units.
Code E1 - an error in the operation of the indoor unit. Lost communication with the controller.
Code E2 - an error in the operation of the temperature sensor.
Code E3 - the temperature sensor of the condenser tube is faulty.
Code E8 - malfunctions in the heating system.
Code F0 - an error in the operation of the internal fan.
Code F2 - the external protection system has tripped.
Code F3 - protection in the high pressure system has tripped.
Code F4 - protection in the low pressure system has tripped.
Code F5 - water overflow protection has tripped.
Code F8 - overheating protection of the outdoor unit has tripped.
Code F9 - incorrect phase sequence. Error in the system.
Code P4 - the compressor of the inverter air conditioner is faulty.
Code P6 - error in the operation of the outdoor EEPROM unit.

Panasonic Error Codes

Error codes for Panasonic brand air conditioners (Panasonic)


H00 – no problems found.
H11 – there is no connection between the external and internal units or there is a problem
control boards.
H12 – the power of the indoor units does not match the outdoor one.
H14 – air sensor short circuit.
H15 – short circuit of the sensor responsible for the temperature of the compressor.
H16 – lack of freon in the external unit or the current circuit is broken
board transformer.
H17 – break in the sensor responsible for the temperature on the tube,
designed to dry out the refrigerant.
H19 – the board, fan motor or connectors are jammed
wires
H21 – the float sensor drainage system is faulty or clogged.
H23 – sensor 1, responsible for the evaporator temperature, is broken.
H24 – sensor 2, responsible for the evaporator temperature, is broken.
H25 – problems with the ionization unit or internal board.
H26 – the ionizer has failed.
H27 – short circuit of the sensor responsible for the outside air temperature.
H28 – short circuit of the sensor responsible for the temperature of the condenser.
H30 – the sensor responsible for the discharge temperature is broken.
H32 – short circuit of the sensor responsible for the temperature of the capacitor at the outlet.
H33 – an error occurred in the interconnect connection.
H34 – short circuit of the sensor responsible for the temperature of the module radiator.
H35 – a pump malfunction or drainage blockage has been detected.
H36 – short circuit of the sensor responsible for the temperature of the gas tube.
H37 – short circuit of the sensor responsible for the temperature of the liquid tube.
H38 – a discrepancy between the outdoor and outdoor units has been detected.
H39 – freon circuits and wires are mixed up, or does not work
solenoid valve.
H41 – wires are connected incorrectly.
H50 – problems with the board or fan motor.
H51 – nozzle clogged.
H52 – limiter switch is faulty.
H58 – Patrol Sensor unit is faulty.
H64 – the sensor responsible for high pressure is faulty.
H97 – problems with the compressor motor or indoor unit board.
H98 – overheating protection is faulty.
H99 – evaporator freezing detected.
F11 - four-way valve does not work correctly.
F17 – indoor unit frozen.
F90 – compressor winding is broken.
F91 - the refrigeration circuit is not working correctly.
F93 – compressor winding is broken.
F94 – supercharger high pressure protection does not work.
F95 – the heat exchanger of the outdoor unit has overheated.
F96 - the power module has overheated.
F97 – compressor temperature exceeded.

Pioneer error codes

Error codes for Pioneer air conditioners

Air conditioner error code Pioneer Yellow diode Green diode
Red diode

Decoding Pioneer air conditioner error
E0 * The function of the discharge temperature sensor is broken
E6 * The function of the capacitor temperature sensor is impaired
E6 * The function of the outdoor air temperature sensor is broken
E1 * The function of the temperature sensor in the room is broken
E2 * The function of the evaporator temperature sensor is impaired
E3 m m m Indoor module fan is broken
E4 m * IPM system failure
E5 m m Power failure
E8 * m m Voltage supply failure
E9 m The compressor started working incorrectly
EA * Incorrect communication with the outdoor module
EC m * The air conditioner is supplied with an electric current of unacceptable parameters
EEPROM failure
EP No communication between external and internal modules
P0 The unit started working incorrectly
P1 Discharge overheating
P2 Increased current in the circuit
P3 Mains voltage too high
P4 m m * No connection with current relay
P5 Evaporator overheating
P6 Condenser overheating
P7 Protection of the IPM matrix
* - diode lights up, m - diode blinks.

Error codes for Pioneer external module air conditioners:

Pioneer air conditioner error code (number of diode blinks) Explanation of Pioneer air conditioner error
1 No connection with external temperature sensor
2 No communication with the capacitor temperature sensor
3 No connection with discharge temperature sensor
4 The current in the electrical network is too high
5 Mains voltage too high
7 No communication with indoor module
9 The unit is not put into operation correctly
12 Mains voltage exceeded
13 IPM board protection
16 Compressor temperature exceeded
17 Discharge temperature too high
18 Condenser temperature too high
19 IPM board failure
20 Communication failure between indoor and outdoor modules
22 De-icing

Quattroclima error codes

Error codes for Quattroclima air conditioners

Error or task
RUN indicator
Digital
display
Cause and troubleshooting
Switching to defrost mode
Flashes 1 time per second
dF
Is not an error.

Preventing cold air supply
Flashes once every 3 seconds
The indoor unit fan does not rotate. This is not an error.
This is a service function of the air conditioner and its settings cannot be changed.
Room temperature sensor error
Flashes 2 times in a row every 4 seconds
E2



Pipe temperature sensor error
Flashes 3 times in a row every 5 seconds
E3
1. Check the resistance of the temperature sensor, if the resistance of the sensor is not normal for the current temperature, replace the sensor.
2. Check sensor connection and circuit integrity
3. The control board is faulty, replace the board.

Outdoor unit error
Flashes 4 times in a row every 6 seconds
E4
1. Check the compressor current and winding resistance.
2. Check the operating pressure. In the event of a refrigerant leak: remove any remaining refrigerant and repair the leak, evacuate the system and charge according to the scale.
3. Check the outdoor unit pipe sensor.
4. Check the condenser of the outdoor unit, it should be clean, free of dust and dirt.
5. Check the operation of the outdoor unit fan.
6. The control board is faulty, replace the board.
Indoor unit fan control error
Flashes 5 times in a row every 7 seconds
E5
1. Check the connectors connecting the fan motor to the control board.
2. Check the indoor fan motor.
3. Check the control board components for damage. Replace damaged components or control board.
Internal board error
Flashes 6 times in a row every 8 seconds
E6
1. Check the indoor unit fan.
2. Check the output signal from the control board. Replace the control board.
Communication error between blocks
Flashes 7 times in a row every 9 seconds
E7
1. Check the inter-unit electrical connection.
2. Check the compressor current and winding resistance.
3. Check operating pressure.
overheat protection
Flashes 8 times in a row every 10 seconds
E8
1. Check the filters, they must be clean.
2. Check the operation of the indoor unit fan.
3. Check the indoor unit pipe sensor.
4. Check operating pressure. In the event of a refrigerant leak: remove any remaining refrigerant and repair the leak, evacuate the system and charge according to the scale.

Samsung Error Codes

Error codes for Samsung air conditioners (Samsung)


E464 – an overload has occurred in the power module.
E461 – the compressor cannot be started.
E473 – the compressor is blocked.
E466 – incorrect voltage in the DC module of the board.
E221 - an error occurred in the sensor responsible for the outside temperature
air.
E416 – overheating detected.
E251 - an error occurred in the temperature sensor.
E468 – an error occurred in the current sensor.
E465 – an error occurred in the operation of the compressor.
E237 - an error occurred in the temperature sensor winding.
E202 – the time allotted for the connection has expired.
E458 – an error occurred in the fan operation.
E471 – an error occurred in the OTP operation.
E467 – an error occurred when rotating the compressor.
E469 – an error occurred in the voltage sensor.
E554 – refrigerant leak detected.
E472 – AC voltage error.
E121 – short circuit in the sensor responsible for the internal air temperature.
E122 – short circuit in the sensor responsible for the evaporator temperature.
E154 – an error occurred in the indoor unit fan.
E101 – time allowed for connection has been exceeded.
E186 – MPI error detected.

Sanyo Error Codes

Error codes for Sanyo air conditioners

E01, E05, E14, E17 – an error occurred when receiving a communication signal;
E02, E04, E06, E10, E20 – an error occurred when transmitting a communication signal;
E03 – an error occurred in the remote control;
E07 – low power level of the indoor unit;
E08 – duplication of setting the destination of the indoor unit has occurred;
E09 – duplication occurred in the control panel settings;
E11 – duplication occurred when carrying out simultaneous multi-control operations;
E15 – high power level of the indoor unit;
E16 – no connection of elements of the indoor unit;
E18 – an error occurred in connecting to MDC;
E31 – errors occurred in the group settings of the indoor unit;
L01 – the types of indoor and outdoor units do not match;
L02 – duplication of the main block occurred in group control;
L03 – address duplication occurred in the outdoor unit;
L04 – group connection has been made for the indoor unit;
L07 – address or group not set;
L08 – power in the indoor unit is not set;
L09 – an error occurred in setting the power of the outdoor unit;
L10 – an error occurred in the connection of the control circuits;
L11 – an error occurred in setting the power of the indoor unit;
L13 – a failure occurred as a result of connecting the ceiling panel;
P01 – malfunction of the float relay;
P03 – there were problems with nutrition;
P05 – no gas;
P09 – overheating occurred;
P10 – there were problems with the discharge temperature;
P15 – 4-code valve blocked;
P19 – cooling overloaded;
P20 – malfunction of the outdoor unit fan;
P22, P26 – malfunctions of the compressor inverter;
P29 – errors in the operation of multi-control when performing simultaneous operations;
P31 – compressor overload;
H01, F02 – malfunction of the temperature sensor of the indoor unit;
F01 – malfunction of the temperature sensor in the outdoor unit;
F04, F06, F07 – temperature violation in the outdoor unit;
F08 – violations in the intake temperature mode;
F10 – violations in the discharge temperature mode;
F12, F29, F31 – errors in the internal non-volatile memory.

TCL Error Codes

Error codes for TCL air conditioners

E0 RUN、TIMER –both winking In and out communication failure. There is no connection between the external and internal units, check the inter-unit connection, the boards of the internal and external units
EC RUN、TIMER –both winking Outdoor communication failure
E1 RUN-1 time/8s Outdoor sensor outdoor sensor
E2 RUN-2 times /8s Indoor coil temperature sensor Evaporator temperature sensor malfunction
E3 RUN-3 times /8s Outdoor coil temperature sensor Condenser temperature sensor faulty
E4 RUN-4 times /8s System abnormity System is faulty
E5 RUN-5 times /8s Type mismatch
E6 RUN-6 times /8s Indoor fan motor Indoor fan motor error
E7 RUN-7 times /8s Outdoor temperature sensor Outdoor unit temperature sensor
E8 RUN-8 times /8s Discharge temperature sensor Compressor discharge temperature sensor
E9 RUN-9 times /8s Invert module abnormity Inverter board is faulty
EF RUN-10 times /8s Outdoor fan motor(DC)
EA RUN-11 times /8s Current sensor
EE RUN-12 times /8s EEPROM failure Malfunction of ROM, firmware.
EP RUN-13 times /8s Top of compressor temperature switch Compressor shut-off thermostat
EU RUN-14 times /8s Voltage sensor
EH RUN-15/8 sec Intake temperature sensor Intake pipe temperature sensor

Emergency stop

P1 RUN: Blink; TIMER: 1 blink /8 sec Overvoltage / undervoltage protection Low/high supply voltage
P2 RUN: Blink; TIMER: 2 blink /8 sec Overcurrent protection
P4 RUN: Blink; TIMER: 4 blink /8 sec Exhaust overtemperature protection Protection against overheating of exhaust gases
P5 RUN: Bright; TIMER: 5 blink /8 sec Subcooling protection under cooling mode Subcooling protection in cooling mode
P6 RUN: Bright; TIMER: 6 blink /8 sec Overheating protection under cooling mode Overheating protection in cooling mode
P7 RUN: Bright; TIMER: 7 blink /8 sec Overheating protection under heating mode Overheating protection under heating mode
P8 RUN: Bright; TIMER: 8 blink /8 sec Outdoor overtemperature / undertemperature protection Outdoor overheating / undercooling protection
P9 RUN: Blink; TIMER: 9 blink /8 sec Drive protection (software control)
P0 RUN: Blink; TIMER: 10 blink /8 sec Module protection (hardware control) Module protection (hardware control)

Toshiba Error Codes

Error codes for Toshiba air conditioners (Toshiba)


00-0C – error in the board of the indoor unit or sensor responsible for
air temperature inside the device.
00-0d – error in the control board or sensor responsible for
radiator temperature.
00-11 – problems with the motor or fan board.
00-12 – repair or replacement of the control board is required.
01-04 – the board or fuses on it have burned out, interconnection
installed incorrectly.
01-05 – an error was detected in the inverter board.
02-14 – overload detected in the inverter.
02-16 – a short circuit occurred in the compressor windings.
02-17 – an error occurred in the current sensor.
02-18 – an error occurred in the temperature sensors.
02-19 – an error occurred in the board temperature sensor.
02-1A - the motor or board is burned out or blocked.
02-1b - a malfunction in the board or sensor responsible for the temperature of the board.
02-1С – the compressor did not have time to start within the allotted time.
03-07 – an error occurred in the inverter board or a defect was noticed
refrigerant.
03-1d – compressor is faulty.
03-1E - an error occurred in the sensor responsible for the suction tube.
03-1F – the refrigeration circuit is overloaded or the voltage in the compressor is low.
03-08 – four-way valve is faulty.

There is “CHEK” on the remote control, press it, point the remote control at the air conditioner and use the temperature arrows to scroll through the codes; on the recorded codes, the air conditioner will produce a signal. This way you will determine the error code, and you can also reset it. If the error is not critical.

Zanussi error codes

Error codes for Zanussi air conditioners

Error codes indicated in the indoor unit
Error code Malfunction Display indication Note
E2 Faulty room temperature sensor TIMER lamp flashes at 5 Hz
E3 Evaporator sensor malfunction START lamp flashes at 5 Hz
E5 Condenser sensor malfunction Defrost lamp flashes at 5 Hz The system will automatically work correctly after the fault is corrected
F5 Drain pan float switch fault Alarm lamp flashes at 5 Hz
F2 Malfunction in the external unit Defrost and alarm lamp flashes at a frequency of 5 Hz
P6 EEPROM malfunction START and TIMER lamps flashing at 5 Hz The system will work normally after a complete shutdown.

Indication of error codes in the Zanussi external unit
Malfunction Indication on the board
Low pressure protection Flashes 4 times every 6 seconds
High pressure protection Flashes 3 times every 5 seconds
Rephase protection Flashes 9 times every 11 seconds
Overcurrent protection Flashes 7 times every 9 seconds
Outside temperature sensor failure Flashes 5 times every 7 seconds
Outdoor heat exchanger overheat protection Flashes 2 times every 4 seconds
Defrost protection Flashes 1 time every 3 seconds
EEPROM error Flashes 8 times every 10 seconds

Both domestic and industrial air conditioning systems, for the most part, have self-diagnosis function. This function can operate in automatic mode or in special mode if problems occur with the equipment. As a rule, information with error codes can be seen on the displays located on the internal units of split systems. Thanks to this data, the malfunctions that caused disruptions in the operation of the air conditioning system are accurately determined. To independently determine the causes of problems in devices from different manufacturers, you can use the lists of error codes for various air conditioners, provided below by brand name.

In LG air conditioning systems, the microprocessor, when any problem is detected, produces unit start blocking, after which it gives signals by blinking LEDs, which indicate the error code.

If the system has detected several problems, then the failure that has the lowest serial number is induced first. After that, faults are indicated in ascending order. The table below lists the error codes for LG air conditioners and explains what each of them means.

You should know: the occurrence of similar errors can be caused by unsatisfactory parameters of the electrical network, or an accidental failure that occurred in the electronics of the unit. Therefore, do not rush to contact service immediately, but simply turn off the power to the device and check the electrical voltage. You also need to make sure that you have selected the correct device operating mode. After these checks, you can turn on the device. Most often, this method helps in solving this problem, and it no longer appears.

The set of fault symbols detected by the microprocessor depends on the unit model. For LG air conditioners there may be another indication - in the form of numbers and letters.

Evaporator unit malfunctions:

Indications of defects in the capacitor unit:

Designations in LG Art Cool units:

Daikin

Daikins are quite complex equipment(from a technical point of view) and, in addition to the refrigeration unit, they have electronic control boards, many different sensors and valves, a power inverter and other components. If any component of the device fails, it is difficult to find the cause of the failure without a special function that allows you to diagnose the equipment. This procedure is carried out using the remote control, and error codes for Daikin air conditioners when the device malfunctions can be seen on its display.

Problems with the evaporator unit of Daikin equipment:





System faults:

Other problems:


Panasonic

Panasonic air conditioner error codes are usually displayed on display located on the wall (room) unit of the unit. They can be recognized by pressing the “CHECK” button on the remote control and holding it for at least 5 seconds.

Since only a hole is visible on the remote control instead of a button, you can use a paper clip, if it is bent, or a small nail to press the recessed button.

After the remote control enters the error checking mode for Panasonic air conditioners, point it towards the indoor unit of the device and by pressing the buttons designed to control the timer (up and down arrows), begin to cycle through the codes, starting from “H00” and further, according to in order. If the fault code matches in the memory of the wall unit and on the remote control, you will hear sound signal. To exit the check mode, press the “CHECK” button again.

Explanation of values ​​for Panasonic units:



Toshiba

The remote control for Toshiba Ras cooling systems also has a “CHECK” button, which enables self-diagnosis of the unit.

Codes for problems in Toshiba household air conditioning systems (Toshiba RAS-07S3KHS-EE/RAS-07S3AHS-EE, Toshiba RAS-10EKV-EE / RAS-10EAV-EE):

These values ​​also apply to devices RAS-10SKHP-ES, RAS-13SKHP-ES, RAS-13S2AH-ES, RAS-07S2AH-ES, RAS-10S2AH-ES, RAS-07SKHP-ES and others.

Fault codes for Toshiba industrial air conditioners:




Ballu

Error codes for Ballu air conditioners are displayed as usual on display indoor evaporator unit. Each time you turn on the Balu air conditioning equipment, the microprocessor conducts self-diagnosis of the equipment and, if problems are detected, displays special symbols on a miniature screen.

Explanation for Ballu brand devices:

Gree

If, when the air conditioner is turned on, the self-diagnosis system detects a malfunction in any module of the device, then its startup is instantly blocked. In this case, all error codes of Gree air conditioners can be observed either on the screen of the remote control or on the display of the internal unit of the unit.

List of faults of Gree air conditioning units:


General Climate

Alphanumeric designations of problems that are highlighted on the remote control:

Errors that are displayed on the wall unit display(internal) General Climate:

Some General Climate air conditioner error codes given above allow the user to independently find the problem and fix it. In other cases, for example, if the def/fan (pre/def) indicator is blinking, specialist assistance will be required.

Samsung

To start self-diagnosis of Samsung equipment, you need to start the condenser in test mode. To do this, hold down the split system start button for 5 seconds. Error codes for Samsung air conditioners, when detected, are displayed on the display of the unit located indoors.

Malfunctions of Samsung split systems:


Mitsubishi

To troubleshoot Mitsubishi equipment, it takes 4 seconds. hold down 2 buttons on the remote control (simultaneously): “CHECK” and “SET”. If problems are detected, error codes for Mitsubishi Electric air conditioners are displayed on the display of the indoor unit or remote control.


In addition to the above errors of the Mitsubishi Electric air conditioner, there are universal error codes related to different models of Mitsubishi Electric units:

  • error E6 or EE - problems were detected in the connection between the unit located outside and the indoor unit. There is no signal from the sensor, or a short circuit is detected;
  • code E5 - malfunctions have been detected during the operation of the equipment; it is also necessary to check the electrical voltage in the network.

Hitachi

The tables below show error codes for Hitachi air conditioners. In Hitachi units, malfunctions are determined by blinking indicators.

TCL

Error codes in TCL climate systems (air conditioners) can be deciphered using the table below (the number of LED blinks in 8 seconds indicates an error code).


Idea

In Idea units, all problems detected by the processor at startup are displayed on the air conditioner display.

With Gree air conditioners and split systems, repairs are easier than with hi-fay series models.

Self-diagnosis of Gree air conditioners

What explains this, the average person may ask?

The explanation is simple Gree: codes. On Gree air conditioners and split systems, there are not many protection system sensors. Those. everything is simplified.

  • Internal self-diagnosis of Gree air conditioners unified and almost identical in error positions to inexpensive air conditioners, such as Pioneer, General Climate, Lessar and others.

You will laugh, but for example, the catalog of Supra air conditioners did not even change the name of the outdoor unit, perhaps you do not have enough skills in Photoshop, perhaps they did not consider it necessary.

In a word, how were Supra air conditioners certified in Russia? It's a mystery to me. Supra Catalog!! In fact. Heh...

Self-diagnosis of Gree air conditioners is, -

  • high pressure protection,
  • protected from freezing of the evaporator,
  • Compressor overload protection,
  • Errors in switching the air conditioner during installation, I confuse the wires,
  • And errors in the evaporator and condenser temperature sensors.

That's it, you'll agree, not much. Gree, like an air conditioner, is functionally simple, so there are not many error codes.
There are disadvantages to this simplification - these are weak varistors on the control board, insufficient smoothing

Error codes table, continued.

currents during voltage surges. A trifle, but this must be kept in mind when repairing air conditioners Gree and their analogues.

Example: country house. When owners leave their dacha, they usually turn off the power to the building using a common switch.
Those. They put it out and that’s it, they calmed down. We arrived... We turned on the lights with the same switch, but the air conditioner, refrigerator, or other household appliances did not work. Why? The answer is simple.

When the power is turned on, current and voltage surges occur with the load.

Varistors that smooth out voltage surges cannot cope with the current load and burn out, burn well with smoke and soot, in the absence of a protective shell, usually together with the fuse of the control board of the internal unit of the split system.

There are “specialists” who use wire when burning a fuse. Is it possible to do this? It’s possible, but then, in addition to the varistors, the control board and the fan motor of the indoor unit will burn out, and... it goes all the way to the compressor windings of the outdoor unit of the air conditioner.

Fireworks at the dacha. — Expensive repairs.

Troubleshooting and air conditioner breakdowns, Gree: as usual, we start with codes...

- refrigeration circuit malfunctions,

- malfunction of the electrical part, electrical system. power supply and air conditioner control.
Source:

Error map, mapping. Primary diagnostics of the system.

GREE Air conditioners for semi-industrial, industrial use - error codes.

Error code = E1
Compressor, pressure surges (sound signal).

Error code = E2
Coil faulty

Error code = E3
Low pressure air conditioning compressor triggered (beep sound)

Error code = F0
Faulty room temperature sensor.

Error code = F1
Incorrect sensor resistance.

Error code = F2

  • The temperature sensor of the outdoor unit of the air conditioner has tripped.

Error code = F3
The temperature sensor circuit is open.

GREE Split air conditioners Error code...

The cause of the malfunction is the refrigerant system with a high degree of protection, pressure.
code = E1

The Gree LED flashes 1 time.
Indicator - cooling =
Heating indicator =

The cause of the Gree malfunction is frost protection.
code = E2

Air conditioner start LED = LED flashes 2 times.
Indicator - cooling =
Heating indicator =

The cause of the malfunction is the high-temperature protection exhaust compressor.
code = E4

Air conditioner start LED = flashes 4 times
Indicator - cooling =
Heating indicator =

Cause of malfunction - AC overcurrent protection
code = E5

Air conditioner start LED = LED flashes 5 times
Indicator - cooling =
Heating indicator =

The cause of the malfunction is a communication failure between the indoor unit of the air conditioner and the outdoor unit of the split system.
code = E6

Gree air conditioner start LED = flashes 6 times
Indicator - cooling =
Heating indicator =

Cause of malfunction - Anti-high temperature protection
code = E8

Air conditioner start LED = flashes 8 times
Indicator - cooling =
Heating indicator =

Cause of malfunction - No feedback of internal fan motor
code = H6

Air conditioner start LED = flashes 11 times
Indicator - cooling =
Heating indicator =

Cause of malfunction - Jumper cap faulty protection
code = C5

Air conditioner start LED = flashes 15 times
Indicator - cooling =
Heating indicator =

Cause of malfunction - Ambient sensor closed, open, no contact or short circuit
code = F1

Indicator, - cooling = LED flashes 1 time
Heating indicator =

Name of malfunction or sensor failure = Indoor tube open, no contact or short circuit
code = F2

Air conditioner start LED =
Indicator, - cooling = LED flashes 2 times
Heating indicator =

Cause of malfunction - external ambient sensor is open, no contact or short circuit
code = F3

Air conditioner start LED =
Indicator, - cooling = LED flashes 3 times
Heating indicator =

Cause of malfunction - Outer tube sensor is open, no contact or short circuit
code = F4

Air conditioner start LED =
Indicator - cooling = flashes 4 times
Heating indicator =

Name = malfunction or breakdown of the exhaust sensor is open, no contact or short circuit
code = F5

Air conditioner start LED =
Indicator, - cooling = LED flashes 5 times
Heating indicator =

Cause of malfunction, - Beyond the maximum load / frequency reduction
code = F6

Air conditioner start LED =
Indicator - cooling = Blink 6 times
Heating indicator =

Cause of malfunction - For current/frequency output limitation
code = F8

Air conditioner start LED =
Indicator - cooling = flashes 8 times
Heating indicator =

Cause of malfunction - High exhaust gas temperature limit / frequency reduction
code = F9

Air conditioner start LED =
Indicator - cooling flash = 9 times
Heating indicator =

Cause of malfunction - Overvoltage protection for RU
code = PH

Air conditioner start LED =
Indicator - cooling = flashes 11 times
Heating indicator =

The cause of the malfunction is AC circuit fault detection
code = U5

Air conditioner start LED =
Indicator - cooling = flashes 13 times
Heating indicator =

Cause of malfunction - Compressor reverse protection
code = U4

Air conditioner start LED =
Indicator - cooling = flashes 14 times
Heating indicator =

Cause of malfunction - For compressor phase current protection
code = P5

Air conditioner start LED =
Indicator - cooling = flashes 15 times
Heating indicator =

The cause of the malfunction is the input malfunction of the sensor tube
code = b5

Air conditioner start LED =
Indicator - cooling = flashes 19 times
Heating indicator =

Cause of malfunction: - Open DC fan motor is faulty.
code = L3

Air conditioner start LED =
Indicator - cooling = flashes 21 times
Heating indicator =

Cause of malfunction - Output fault or tube sensor failure
code = b7

Air conditioner start LED =
Indicator - cooling = flash 22 times
Heating indicator =

Cause of malfunction - Compressor overload sensor is faulty.
code = FE

Air conditioner start LED =
Indicator - cooling =
Heating indicator =

Cause of malfunction - Defrosting
code = h3

Air conditioner start LED =
Indicator - cooling =
Heating indicator = LED flashes 1 time

The cause of the malfunction is static dust protection cleaning
code = H2

Air conditioner start LED =
Indicator - cooling =
Heating indicator = LED flashes 2 times

Cause of malfunction - Compressor overload protection
code = H3

Air conditioner start LED =
Indicator - cooling =
Heating indicator = LED flashes 3 times

Cause of malfunction - System abnormal protection
code = H4

Air conditioner start LED =
Indicator - cooling =
Heat indicator = flashes 4 times

Cause of malfunction - IPM protection
code = H5

Air conditioner start LED =
Indicator - cooling =
Heating indicator = LED flashes 5 times

Cause of malfunction - PFC protection
code = HC

Air conditioner start LED =
Indicator - cooling =
Heat indicator = flashes 6 times

Cause of malfunction - Compressor loss of protection step
code = H7

Air conditioner start LED =
Indicator - cooling =
Heating indicator flashes = 7 times

Cause of malfunction - Heating against high frequency temperature drop
code = HO

Air conditioner start LED =
Indicator - cooling =
Heat indicator = flashes 10 times

Cause of malfunction - Startup failure
code = Lc

Air conditioner start LED =
Indicator - cooling =
Heat indicator = flashes 11 times

Cause of malfunction - Phase loss protection compressor
code = U2

Air conditioner start LED =
Indicator - cooling =
Heat indicator = flashes 12 times

Cause of malfunction - Phase current compressor detection circuit faulty
code = U1

Air conditioner start LED =
Indicator - cooling =
Heat indicator = flashes 13 times

Cause of malfunction - Compressor demagnetization protection
code = HE

Air conditioner start LED =
Indicator - cooling =
Heat indicator = flashes 14 times

Cause of failure - Loading EEPROM is faulty.
code = EE

Air conditioner start LED =
Indicator - cooling =
Heat indicator = flashes 15 times

The cause of the malfunction is a communication failure between the motherboard and the board driver
code = P6

Air conditioner start LED =
Indicator - cooling =
Heat indicator = flashes 16 times

The cause of the malfunction is a faulty charging capacitor
code = PU

Air conditioner start LED =
Indicator - cooling =
Heat indicator = flashes 17 times

The cause of the malfunction is that the sensor circuit IPM is faulty.
code = P7

Air conditioner start LED =
Indicator - cooling =
Heat indicator = flashes 18 times

The cause of the malfunction is IPM high-temperature protection
code = P8

Air conditioner start LED =
Indicator - cooling =
Heat indicator = flashes 19 times

Cause of malfunction - PN protection voltage drop
code = U3

Air conditioner start LED =
Indicator - cooling = flashes 20 times
Heating indicator =

The cause of the malfunction is low PN voltage protection
code = PL

Air conditioner start LED =
Indicator - cooling =
Heat indicator = flashes 21 times

The cause of the malfunction is the current detection circuit is faulty or the current sensor is faulty or broken.
code = Rs

Air conditioner start LED =
Indicator - cooling =
Heating indicator =

Cause of malfunction - Compressor phase failure protection
code = Ld

Air conditioner start LED =
Indicator - cooling =
Heating indicator =

Cause of malfunction - Compressor or rotary protection blocked
code = LE

Air conditioner start LED =
Indicator - cooling =
Heating indicator =

Cause of malfunction - IPM exceeds temperature limit / frequency decrease
code = EU

Air conditioner start LED =
Indicator - cooling =
Heating indicator =

Cause of malfunction - 4-way reversal valve abnormal
code = U7

Air conditioner start LED =
Indicator - cooling =
Heating indicator =

The cause of the malfunction is the disconnection of the exhaust gas temperature sensor
code = U8

Air conditioner start LED =
Indicator - cooling =
Heating indicator =

Cause of fault, - AC zero voltage detection error
code = U9

Air conditioner start LED =
Indicator - cooling =
Heating indicator =

The cause of the malfunction is the frequency temperature difference behind the tubes
code = FA

Air conditioner start LED =
Indicator - cooling =
Heating indicator =

Cause of malfunction - Anti-freeze limit / frequency reduction
code = FH

Air conditioner start LED =
Indicator - cooling =
Heating indicator =

Models: air conditioner repair brands KFR-32GW/BP, KFR-45LW/D, KFR-3502GW/BP, KFR-2501GW, KFR-45LW, KFR-3301GW, KFR-3201GWCPU, KFR-2608GW/BP and other KFR series,PDF fail.